beautypg.com

Spectrum Controls 1769sc-HART Modules User Manual

Page 60

background image

Compact IO™ Isolated HART Analog Output Module

User’s Manual 0300217-03 Rev. A

6-8

Data Format

This selection allows the user to define the channel’s data format for any of the
following:

Raw/Proportional Data

The raw/proportional data format provides the best resolution of all the
supported data formats.

If you select the raw/proportional data format for a channel, the output
command word

1

will be a number between -32767 and +32767. For example, if

a 4 to 20 mA output type is selected, 4 mA corresponds to -32767 counts and 20
mA corresponds to +32767.

Engineering Units

When using this data format, the module scales the output command word

1

to

the actual engineering values for the selected output type. Values are expressed
with an assumed decimal place. Refer to Table 6-8 (Data Formats).

The resolution for the selected data format is dependent on the output type
selected.

Scaled-for-PID

The PID algorithm for the MicroLogix 1500 and other Allen-Bradley controllers
(i.e. SLC) utilize an engineering range of 0 to 16383. The scaled for PID format
allows the programmer to assign the output command word

1

for the selected

channel directly to the PID instruction’s CV variable, thus eliminating the need
for further scaling.

Percent Range

The output command word

1

for the selected channel is scaled using a range of 0

to +10000 counts. For example, if a 4 to 20 mA output type is selected, 4 mA
corresponds to 0 counts and 20 mA corresponds to +10000 counts.

Note: 10000 counts represent 100.00 percent.

Table 6-5 (Data Formats)

Output Type

Engineering

Scaled for PID Proportional Counts

Percent

0 – 20 mA

0 to 20000

0 to 16383

-32768 to 29646

0 to 10000

4 – 20 mA

4000 to 20000

0 to 16383

-29822 to 29085

0 to 10000


Reserved

Reserved for future expansion and should be set to zero.

6.3.14 Fault Value (Words 2, 10, 18, 26)

During a processor fault condition, the associated output channel will be driven to this
value.

Note: The range of this value is defined by the data format selected for the channel.

6.3.15 Program/Idle Value (Words 3, 11, 19, 27)

During a processor program or idle mode, the associated output channel will be driven to
this value.

1

Module output words 0 through 3 for channel 0 through 3, respectively.