Chapter 6
Module Data, Status, and
Channel Configuration
After installing the 1769sc-OF4IH isolated HART output module, you must configure it
for operation, usually using the programming software compatible with the controller (for
example, RSLogix 500 or RSLogix 5000). Once configuration is complete and reflected
in the ladder logic, you need to operate the module and verify its configuration.
This chapter contains information on the following:
Module memory map
Accessing input image file data
Configuring channels
Determining effective resolution and range
Determining module update time
Section 6.1
Module Memory
Map
The module uses forty eight input words for data and status bits (input image), twenty
eight output words, and forty two configuration words.
Figure 6-1 (Module Memory Map)
NOTE: Not all
controllers support
program access to the
configuration file. Refer
to your controller’s user
manual.
slot e
Input Image File
Input Image
70 Words
Memory Map
Word 0: Status Word 0
Word 1: Status Word 1
Word 2: Channel 0 Data Value
Word 3: Channel 1 Data Value
Word 4: Channel 2 Data Value
Word 5: Channel 3 Data Value
Words 6..25: HART Data
Word 26: Message Slave Control
Word 27: Response Size
Words 28..47: Message Response Buffer
Bit 15
Bit 1
slot e
Configuration File
Configuration
42 Words
Words 16..23: Channel 2 Configuration
Words 24..31: Channel 3 Configuration
Word 32: Pad
Word 33: HART Configuration Word
Bit 15
Bit 1
Words 8..15: Channel 1 Configuration
Words 0..7: Channel 0 Configuration
slot e
Output File
Output
50 Words
Word 2: Channel 2 Output Value
Word 3: Channel 3 Output Value
Word 4: Channel Alarm Unlatch
Bit 15
Bit 1
Word 1: Channel 1 Output Value
Word 0: Channel 0 Output Value
Word 34: Ch0 Slot Variables 0 & 1
Word 35: Ch0 Slot Variables 2 & 3
Word 36: Ch1 Slot Variables 0 & 1
Word 37: Ch1 Slot Variables 2 & 3
Word 38: Ch2 Slot Variables 0 & 1
Word 39: Ch2 Slot Variables 2 & 3
Word 40: Ch3 Slot Variables 0 & 1
Word 41: Ch3 Slot Variables 2 & 3
Word 5: HART Packet Just Scanned
Word 6: Message Master Control
Word 7: Request Size
Words 8..27: Message Request Buffer
Words 48..69: Reserved
Words 28..49: Reserved