beautypg.com

Spectrum Controls 1769sc-HART Modules User Manual

Page 53

background image

User’s Manual 0300217-03 Rev. A

Chapter 6
Module Data, Status, and
Channel Configuration

After installing the 1769sc-OF4IH isolated HART output module, you must configure it
for operation, usually using the programming software compatible with the controller (for
example, RSLogix 500 or RSLogix 5000). Once configuration is complete and reflected
in the ladder logic, you need to operate the module and verify its configuration.

This chapter contains information on the following:

 Module memory map

 Accessing input image file data

 Configuring channels

 Determining effective resolution and range

 Determining module update time

Section 6.1
Module Memory
Map

The module uses forty eight input words for data and status bits (input image), twenty
eight output words, and forty two configuration words.

Figure 6-1 (Module Memory Map)

NOTE: Not all
controllers support
program access to the
configuration file. Refer
to your controller’s user
manual.

slot e

Input Image File

Input Image

70 Words

Memory Map

Word 0: Status Word 0

Word 1: Status Word 1

Word 2: Channel 0 Data Value

Word 3: Channel 1 Data Value

Word 4: Channel 2 Data Value

Word 5: Channel 3 Data Value

Words 6..25: HART Data

Word 26: Message Slave Control

Word 27: Response Size

Words 28..47: Message Response Buffer

Bit 15

Bit 1

slot e

Configuration File

Configuration

42 Words

Words 16..23: Channel 2 Configuration

Words 24..31: Channel 3 Configuration

Word 32: Pad

Word 33: HART Configuration Word

Bit 15

Bit 1

Words 8..15: Channel 1 Configuration

Words 0..7: Channel 0 Configuration

slot e

Output File

Output

50 Words

Word 2: Channel 2 Output Value

Word 3: Channel 3 Output Value

Word 4: Channel Alarm Unlatch

Bit 15

Bit 1

Word 1: Channel 1 Output Value

Word 0: Channel 0 Output Value

Word 34: Ch0 Slot Variables 0 & 1

Word 35: Ch0 Slot Variables 2 & 3

Word 36: Ch1 Slot Variables 0 & 1

Word 37: Ch1 Slot Variables 2 & 3

Word 38: Ch2 Slot Variables 0 & 1

Word 39: Ch2 Slot Variables 2 & 3

Word 40: Ch3 Slot Variables 0 & 1

Word 41: Ch3 Slot Variables 2 & 3

Word 5: HART Packet Just Scanned

Word 6: Message Master Control

Word 7: Request Size

Words 8..27: Message Request Buffer

Words 48..69: Reserved

Words 28..49: Reserved