Spectrum Controls 1769sc-HART Modules User Manual
Page 110
Compact IO™ Isolated HART Analog Output Module
User’s Manual 0300217-03 Rev. A
7-44
Table 7-19
Tag Nam e
Value in Hex
Description
HART_PASS_THRU_QRY_RX[0]
00
HART channel
HART_PASS_THRU_QRY_RX[1]
00
Command Status
HART_PASS_THRU_QRY_RX[2]
15
Length of handle + HART response
data (Byte 1)
HART_PASS_THRU_QRY_RX[3]
0
Length of handle + HART response
data (Byte 2)
HART_PASS_THRU_QRY_RX[4]
02
Message handle
HART_PASS_THRU_QRY_RX[5]
86
Start charcter
HART_PASS_THRU_QRY_RX[6]
BE
Long address byte 0
HART_PASS_THRU_QRY_RX[7]
02
Long address byte 1
HART_PASS_THRU_QRY_RX[8]
0C
Long address byte 2
HART_PASS_THRU_QRY_RX[9]
77
Long address byte 3
HART_PASS_THRU_QRY_RX[10]
37
Long address byte 4
HART_PASS_THRU_QRY_RX[11]
23
HART command = 35 decimal
HART_PASS_THRU_QRY_RX[12]
0B
Byte count = 11 decimal
HART_PASS_THRU_QRY_RX[13]
00
Status Byte 0
HART_PASS_THRU_QRY_RX[14]
00
Status Byte 1
HART_PASS_THRU_QRY_RX[15]
20
Range units code = 32 decimal
HART_PASS_THRU_QRY_RX[16]
44
HART_PASS_THRU_QRY_RX[17]
16
HART_PASS_THRU_QRY_RX[18]
00
HART_PASS_THRU_QRY_RX[19]
00
HART_PASS_THRU_QRY_RX[20]
C3
HART_PASS_THRU_QRY_RX[21]
16
HART_PASS_THRU_QRY_RX[22]
00
HART_PASS_THRU_QRY_RX[23]
00
HART_PASS_THRU_QRY_RX[24]
F9
Checksum
Upper Range value (This is a
floating point value = 600) Note: The
bytes are in reverse order.
Low er Range value (This is a
floating point value = -150) Note:
The bytes are in reverse order.