• Compare the value measured with the values indicated in the
table below.
Gas adjustment
G20
G31
CO2 case ON
9 ± 0.2 %
10.1 ± 0.2 %
CO2 case OFF
9.2 ± 0.3 %
10.3 ± 0.3 %
i
Safe combustion can only be verified by measuring
CO/CO2 ratio. This must not exceed the value
shown in the table under the section "Maximum Rate
and Adjustment".
16.1.3
Restarting
• Replace the cap
• Replace the appliance front panel.
Note: following the replacement of the front panel, the CO2
value will change: you can check that the value "case on" is
correct by the values in the previous table.
1
2
Key
1 Serial number stickers
2 Data label location
• Firmly attach the gas replacement label to the appliance in
the corresponding location (1) on the electrical box.
16.2 Restart - re-check commissioning
• Before putting the appliance into operation, follow the
instructions within the chapter Specific adjustment.
17 Draining
17.1 Heating circuit
B
A
1
2
Key
1 Length of hose (not supplied)
2 Drain valve
• Drain down the heating circuit of the boiler only, by closing
the heating flow and return isolating valves. See chapter
"Hydraulic connection ► Gas and water connections"
• Attach a length of hose (1) to the drain point and open the
drain valve (2).
• After draining, close the drain valve (2) and remove the hose.
17.2 Domestic Hot water circuit
• Drain the Domestic Hot Water circuit by closing the cold-
water isolation valve on the wall mounting jig.
• Open one or more hot water taps to drain the hot water
circuit.