beautypg.com

KEYENCE DL-EP1 User Manual

Page 109

background image

5-5 Objects Usable by DL-EP1

5-21

Identity Object

5

App

end
ix

- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (GT2) -

Reset service

The Reset service is a CIP standard function used to emulate the same operations as
power restart as much as possible. When it accepts this service, the DL-EP1 stops

each function, interrupts communication, and reads the settings again. The Reset

service is used as a restart request for reflecting changed parameters (e.g., IP
address, Ethernet communication speed, etc.).

Execute this service by designating 01H as the Instance ID of the Identity object.

• The commands received during Reset processing may be discarded.
• The response for the Reset service is returned before the DL-EP1 starts

reset processing.

„

List of general and additional statuses returned to each service

Service Code

Service Name

Service Data (1 Byte)

05H

Reset

00H: Emulates power reset. (Initial value)

01H: Restores the default settings and emulates power reset.
For details on the default settings, refer to

"Default

Settings" (Page 5-5).
• If the DL-EP1 receives the Reset service when 02H or

higher is set, 03H (Invalid parameter value) is returned as

the CIP error code.

Point

Service

General

Status

Additional

(Extended)

Status

Description

Get_Attributes_

All

00H

-

The service has ended normally.

05H

-

The designated instance ID does not exist.

Reset

00H

-

The service has ended normally.

03H

-

The designated reset method is incorrect.

05H

-

The designated instance ID does not exist.

Get_Attribute_

Single

00H

-

The service has ended normally.

05H

-

The designated instance ID does not exist.

14H

-

The designated attribute ID does not exist.

Others

08H

-

The designated service is not supported.