Programming FA416, FA416D and FA464 Receivers
Press ENTER to review or to modify output settings.
Press
!
to go to PROGRAM POINTS menu option or
"
to go to RCVR
SETUP.
Press
ENTER to advance through all numbered outputs.
Press
!
or
"
to select from options ALARM,
ALARM+TAMPER, TAMPER, LO BATT, INACTVE,
TAMP+LOBATT, TAMP+INACTVE, BATT+INACTVE, ANY
TX FAULT, and DISABLED.
Note: ALARM and ALARM+TAMPER are point-specific: points programmed to a given output will trip the
output if alarmed or if tampered. All other fault options are global; i.e., any listed fault (or combination of faults)
will cause the output to activate. Attempts to assign duplicate global fault conditions to other outputs are not
allowed.
Global faults will be indicated.
If an output is modified to function as a global fault output and is currently assigned to an active point, the user
will be prompted for permission to re-assign the output:
When output setup is complete, points affected by re-assignment will be shown.
Note: "Follower" outputs go on and off as the transmitter changes between alarm and secure states. "Latching"
outputs go on at first activation, and stay on until reset. "Momentary" outputs go on for a prescribed
duration then turn off, regardless of what the transmitter does after first activation.
Press
!
or
"
to select from options FOLLOWER, MOMENTARY or
LATCHING.
Press
!
or
"
to select from options FOLLOWER, MOMENTARY or
LATCHING.
Press
!
or
"
to select from options FOLLOWER, MOMENTARY or
LATCHING.
Press
!
or
"
to select from options FOLLOWER, MOMENTARY or
LATCHING.
If any outputs are programmed MOMENTARY, the user will be prompted for the number of seconds of
momentary activation.
Enter a value from 1 to 16 seconds.
OUTPUT nn:
!
ALARM
"
OUTPUT 1: GLOBL
!
TAMP+LO BATT
"
OUTPUT 1 IN USE
REASSIGN?
!
YES
"
CHECK POINT 1
OUTPUT ASSIGNM'T
LO BATT OUTPUT
!
LATCHING
"
INACTIVE OUTPUT
!
FOLLOWER
"
MOMENTARY OUTPUT
TIME: 4 secs
TAMPER OUTPUT
!
FOLLOWER
"
ALARM OUTPUTS
!
FOLLOWER
"
Press ENTER for
!
OUTPUT SETUP
"
Output
Setup