beautypg.com

Electric heaters – Bryant 548J User Manual

Page 24

background image

24

Shorting the jumpers for a period of 5 to 20 secs bypasses

the remaining continuous run period and places the unit in

a Forced Defrost mode. If the controlling DFT is closed

when this mode is initiated, the unit will complete a

normal defrost period that will terminate when the

controlling DFT opens or the 10 minute defrost cycle limit

is reached. If the controlling DFT is open when this mode

is initiated, the Defrost cycle will run for 30 secs. Both

modes end at the end of the Defrost cycle.

ELECTRIC HEATERS

548J units may be equipped with field--installed accessory

electric heaters. The heaters are modular in design, with

heater frames holding open coil resistance wires strung

through ceramic insulators, line--break limit switches and

a control contactor. One or two heater modules may be

used in a unit.

DISCONNECT MOUNTING
LOCATION

UNIT BLOCK-OFF
PANEL

OUTDOOR
ACCESS PANEL

INDOOR
ACCESS
PANEL

C08133

Fig. 29 -- Typical Access Panel Location (3--6 Ton)

Heater modules are installed in the compartment below

the indoor (supply) fan outlet. Access is through the

indoor access panel. Heater modules slide into the

compartment on tracks along the bottom of the heater

opening. See Fig. 29, Fig. 30 and Fig. 31.
Not all available heater modules may be used in every

unit. Use only those heater modules that are UL listed for

use in a specific size unit. Refer to the label on the unit

cabinet re approved heaters.

Unit heaters are marked with Heater Model Numbers. But

heaters are ordered as and shipped in cartons marked with

a corresponding heater Sales Package part number. See

Table 11 for correlation between heater Model Number

and Sales Package part number.
NOTE: The value in position 9 of the part number differs
between the sales package part number (value is 1) and a

bare heater model number (value is 0).

DISCONNECT
MOUNTING
LOCATION

EMT OR RIGID CONDUIT
(FIELD-SUPPLIED)

SINGLE
POINT BOX

CENTER
POST

HEATER
COVERS

HEATER
MOUNTING
BRACKET

HEATER
MODULE
(LOCATION 2)

HEATER
MODULE
(LOCATION 1)

SINGLE POINT
BOX
MOUNTING
SCREW

BRACKET AND
CONDUIT
DRIP BOOT

MAIN
CONTROL
BOX

CONTROL WIRE TERMINAL BLOCK

MANUAL RESET
LIMIT SWITCH

C08134

Fig. 30 -- Typical Component Location

TRACK

FLANGE

C08135

Fig. 31 -- Typical Module Installation

Table 11 – Heater Model Number

Bare Heater Model Number

C

R

H

E

A

T

E

R

0

0

1

A

0

0

Heater Sales Package PNO

Includes:

Bare Heater

Carton and packing materials

Installation sheet

C

R

H

E

A

T

E

R

1

0

1

A

0

0

548J