beautypg.com

Caution, Puron, R a) refrigerant – Bryant 548J User Manual

Page 13

background image

13

PURON

R

(R--410A) REFRIGERANT

This unit is designed for use with Puron (R--410A)

refrigerant. Do not use any other refrigerant in this

system.

Puron (R--410A) refrigerant is provided in pink (rose)

colored cylinders. These cylinders are available with and

without dip tubes; cylinders with dip tubes will have a

label indicating this feature. For a cylinder with a dip

tube, place the cylinder in the upright position (access

valve at the top) when removing liquid refrigerant for

charging. For a cylinder without a dip tube, invert the

cylinder (access valve on the bottom) when removing

liquid refrigerant.

Because Puron (R--410A) refrigerant is a blend, it is

strongly recommended that refrigerant always be removed

from the cylinder as a liquid. Admit liquid refrigerant into

the system in the discharge line. If adding refrigerant into

the suction line, use a commercial metering/expansion

device at the gauge manifold; remove liquid from the

cylinder, pass it through the metering device at the gauge

set and then pass it into the suction line as a vapor. Do not

remove Puron (R--410A) refrigerant from the cylinder as a

vapor.

Refrigerant Charge

Amount of refrigerant charge is listed on the unit’s

nameplate. Refer to the GTAC2--5 Charging, Recovery,

Recycling and Reclamation training manual and the

following procedures.

Unit panels must be in place when unit is operating during

the charging procedure. If unit is equipped with a head

pressure control device, bypass it to ensure full fan

operation during charging.

Charge checking and adjustments must be made while the

system is operating in Cooling only.
No Charge
Use standard evacuation techniques for Puron (R--410A)

refrigerant.. After evacuating system, weigh in the

specified amount of refrigerant.
Low--Charge Cooling
Using Cooling Charging Charts, Fig. 20 vary refrigerant

until the conditions of the appropriate chart are met. Note

the charging charts are different from type normally used.

Charts are based on charging the units to the correct

superheat for the various operating conditions. Accurate

pressure gauge and temperature sensing device are

required. Connect the pressure gauge to the service port

on the suction line. Mount the temperature sensing device

on the suction line and insulate it so that outdoor ambient

temperature does not affect the reading. Indoor--air cfm

must be within the normal operating range of the unit.

To Use Cooling Charging Charts
Take the outdoor ambient temperature and read the

suction pressure gauge. Refer to chart to determine what

suction temperature should be. If suction temperature is

high, add refrigerant. If suction temperature is low,

carefully recover some of the charge. Recheck the suction

pressure as charge is adjusted.

SIZE DESIGNATION

NOMINAL TONS

REFERENCE

04A

3

05A

4

06A

5

07A

6

08D

7.5

09D

8.5

EXAMPLE:
Model 548J*04A
Outdoor Temperature

85_F (29_C)

. . . . . . . . . . . . . . . . . .

Suction Pressure

140 psig (965 kPa)

. . . . . . . . . . . . . . . . .

Suction Temperature should be

55_F (13_C)

. . . . . . . . . .

Compressors

Lubrication
Compressors are charged with the correct amount of oil at

the factory.

UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to

components.
The compressor is in a PuronR refrigerant system and

uses a polyolester (POE) oil. This oil is extremely

hygroscopic, meaning it absorbs water readily. POE

oils can absorb 15 times as much water as other oils

designed for HCFC and CFC refrigerants. Avoid

exposure of the oil to the atmosphere.

CAUTION

!

Replacing Compressor
The compressor used with Puron refrigerant contains a

POE oil. This oil has a high affinity for moisture. Do not

remove the compressor’s tube plugs until ready to insert

the unit suction and discharge tube ends.

Compressor mounting bolt torque is 65--75 in--lbs (7.3--8.5

Nm).

548J