Bryant LEGACY LINE 580J User Manual
Page 34

34
Table 18 – COOLING CAPACITIES
1--STAGE COOLING
5 TONS
580J06 (5 TONS) --- UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE
Air Entering Evaporator --- CFM
Temp (F) Air Ent
Condenser (Edb)
80 dry bulb
80 dry bulb
80 dry bulb
72 wet bulb
67 wet bulb
62 wet bulb
1750
2000
2250
1750
2000
2250
1750
2000
2250
75
TC
73.1
78.7
84.5
63.2
66.9
70.8
53.2
55.1
57.1
SHC
35.3
37.2
38.8
42.0
43.7
45.3
48.7
50.3
51.8
kW
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
85
TC
67.6
71.2
75.0
59.1
61.2
63.3
50.6
51.1
51.5
SHC
27.9
30.0
31.9
36.3
38.3
40.1
44.8
46.6
48.2
kW
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
95
TC
62.1
63.8
65.5
55.1
55.4
55.8
48.0
47.0
46.0
SHC
20.5
22.9
24.9
30.7
32.9
34.8
40.9
42.9
44.7
kW
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
105
TC
56.6
56.3
56.0
51.0
49.6
48.3
45.4
43.0
40.5
SHC
13.1
15.7
18.0
25.0
27.5
29.6
36.9
39.2
41.2
kW
4.8
4.8
4.8
4.8
4.8
4.8
4.7
4.7
4.7
115
TC
51.1
48.8
46.5
46.9
43.9
40.7
42.8
39.0
35.0
SHC
5.8
8.6
11.0
19.4
22.0
24.4
33.0
35.5
37.7
kW
5.3
5.3
5.3
5.3
5.3
5.3
5.2
5.2
5.2
580J06 (5 TONS) --- UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE
Air Entering Evaporator --- CFM
Temp (F) Air Ent
Condenser (Edb)
75 dry bulb
75 dry bulb
75 dry bulb
62.5 wet bulb (50% relative)
64 wet bulb (55% relative)
65.3 wet bulb (60% relative)
1750
2000
2250
1750
2000
2250
1750
2000
2250
80
TC
23.0
24.4
25.6
24.7
26.2
27.4
26.3
27.7
29.0
SHC
5.3
6.1
6.8
3.2
4.0
4.7
1.4
2.2
2.9
kW
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
75
TC
23.3
24.6
25.7
25.0
26.3
27.5
26.4
27.8
29.0
SHC
5.1
5.8
6.5
3.1
3.9
4.5
1.4
2.2
2.8
kW
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
70
TC
23.5
24.8
25.9
25.2
26.4
27.5
26.6
27.9
29.0
SHC
4.8
5.5
6.2
3.0
3.7
4.3
1.4
2.1
2.8
kW
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
60
TC
24.1
25.2
26.1
25.6
26.7
27.7
26.9
28.0
29.0
SHC
4.3
5.0
5.5
2.8
3.4
3.9
1.4
2.0
2.6
kW
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
50
TC
24.7
25.6
26.4
26.1
27.0
27.8
27.2
28.2
29.0
SHC
3.8
4.4
4.8
2.5
3.1
3.5
1.4
2.0
2.4
kW
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
40
TC
25.3
26.0
26.7
26.5
27.3
27.9
27.6
28.3
29.0
SHC
3.3
3.8
4.2
2.3
2.8
3.1
1.4
1.9
2.3
kW
3.1
3.1
3.1
3.2
3.2
3.2
3.2
3.2
3.2
LEGEND
Edb --- Entering Dry---Bulb
Ewb --- Entering Wet---Bulb
kW
--- Compressor Motor Power Input
Idb
--- Leaving Dry---Bulb
Iwb --- Leaving Wet---Bulb
SHC --- Sensible Heat Capacity (1000 Btuh) Gross
TC
--- Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
t
ldb
= t
edb
–
sensible capacity (Btuh)
1.10 x cfm
t
lwb
= Wet---bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h
lwb
)
h
lwb
= h
ewb
–
total capacity (Btuh)
4.5 x cfm
Where: h
ewb
= Enthalpy of air entering evaporator coil
580J