beautypg.com

Curbs & weights dimensions j 14 (cont.) – Bryant LEGACY LINE 580J User Manual

Page 24

background image

24

CURBS & WEIGHTS DIMENSIONS -- 580J 14 (cont.)

C08528

Fig. 10 -- Dimensions 580J--14

C

B

A

D

C08337

Fig. 11 -- Service Clearance

LOC

DIMENSION

CONDITION

A

48---in (1219 mm) Unit disconnect is mounted on panel

36---in (914 mm)

If dimension---B is 12---in (305 mm)

18---in (457 mm)

No disconnect, convenience outlet option

18---in (457 mm)

Recommended service clearance (use electric screwdriver)

12---in (305 mm)

Minimum clearance (use manual ratchet screwdriver)

B

36---in (914 mm)

Unit has economizer

12---in (305 mm)

If dimension---A is 36---in (914 mm)

Special

Check for sources of flue products within 10---ft of unit fresh air intake hood

C

36---in (914 mm)

Side condensate drain is used

18---in (457 mm)

Minimum clearance

D

48---in (1219 mm) No flue discharge accessory installed, surface is combustible material
42---in (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)

36---in (914 mm)

Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)

Special

Check for adjacent units or building fresh air intakes within 10---ft of this unit’s flue outlet

580J