CURBS & WEIGHTS DIMENSIONS -- 580J 14 (cont.)
C08528
Fig. 10 -- Dimensions 580J--14
C
B
A
D
C08337
Fig. 11 -- Service Clearance
LOC
DIMENSION
CONDITION
A
48---in (1219 mm) Unit disconnect is mounted on panel
36---in (914 mm)
If dimension---B is 12---in (305 mm)
18---in (457 mm)
No disconnect, convenience outlet option
18---in (457 mm)
Recommended service clearance (use electric screwdriver)
12---in (305 mm)
Minimum clearance (use manual ratchet screwdriver)
B
36---in (914 mm)
Unit has economizer
12---in (305 mm)
If dimension---A is 36---in (914 mm)
Special
Check for sources of flue products within 10---ft of unit fresh air intake hood
C
36---in (914 mm)
Side condensate drain is used
18---in (457 mm)
Minimum clearance
D
48---in (1219 mm) No flue discharge accessory installed, surface is combustible material
42---in (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
36---in (914 mm)
Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)
Special
Check for adjacent units or building fresh air intakes within 10---ft of this unit’s flue outlet