Interconnecting wiring, Logicool ™ onrak active cabinet exhaust it cooling, It cooling – Airedale OnRak 3kW 35kW User Manual
Page 40

LogiCool
™ OnRak
Active Cabinet Exhaust
IT Cooling
40
IT Cooling
Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013
Interconnecting Wiring
OnRak
L1
Mains incoming supply 230V/1PH/50Hz
N1
PE
509
Flow solenoid valve
500
Common
509
Return solenoid valve
500
Common
824
Signal to chilled water valve
500
Common
502
24VAC
827
Air on temperature
828
Air on humidity
502
24VAC
500
Common
SCR
Screened cable terminated at controller.
561
Critical Alarm
Volt Free Common Alarm
560
Volt Free Alarm N/O
562
Volt Free Alarm N/C
564
Non Critical Alarm
Volt Free Common Alarm
563
Volt Free Alarm N/O
RX-/Tx-
Use Awg20/22 twisted pair (with overall shield) cable, Belden
ref. 8762 (Airedale ref: 6110316), or equivalent, for
network
Network Connections (Inward connection)
RX+/Tx+
GND
RX-/Tx-
Use Awg20/22 twisted pair (with overall shield) cable, Belden
ref. 8762 (Airedale ref: 6110316), or equivalent, for
network
Network Connections (Outward connection)
RX+/Tx+
GND