beautypg.com

Mechanical data, Electrical data, Waterside pressure drop – Airedale OnRak 3kW 35kW User Manual

Page 18: Logicool ™ onrak active cabinet exhaust it cooling

background image




LogiCool

™ OnRak



Active Cabinet Exhaust

IT Cooling

18

IT Cooling

Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013

Mechanical Data

LOR6042U-C028-0

LOR6042U-C033-0

LOR8042U-C032-0

LOR8042U-C038-0

Dimensions - H x W x D

mm

2030 x 600 x203

2030 x 600 x 203

2032 x 800 x 213

2032 x 800 x 213

Weight - Machine

– Operating

kg

65

75

65

75

96

110

96

110

Construction

Sheet steel, epoxy baked powder paint

Material/ Colour

RAL 7021 (Black Grey)

Nominal Air flow

m³/s

1.4

1.8

1.4

1.8

Fan redundancy

N+1

N

N+1

N

Gross Total cooling Capacity

(1)

kW

28.1

33.4

32.0

38.5

Fan gains

W

161

306

161

306

EER

175

109

199

126

(1) Based upon a server discharge temperature of 45°C. Water on 13°C, Water off 19°C. 100% water

Electrical Data

LOR6042U-C028-0

LOR6042U-C033-0

LOR8042U-C032-0

LOR8042U-C038-0

Nominal Run Amps

(1)

1.35

1.52

1.35

1.52

Maximum Run Amps

(1)

1.62

1.62

1.62

1.62

Recommended Mains Fuse Size

A

10

10

10

10

Mains Supply

V

230

230

230

230

Control Circuit

VAC

24

24

24

24

Motor Type

EC Axial

Quantity x Motor Size

W

4 x 72

4 x 72

4 x 72

4 x 72

Power input

W

161

306

161

306

(1) Measured on a basic unit including 3 way valves.

Note: Earth Leakage current from the OnRak may exceed 3mA

Waterside Pressure Drop

0

50

100

150

200

250

300

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

Water flow rate l/s

P

ressu

re d

rop

kP

a

LOR6042

LOR8042

Coil, Hose and Valve Pressure Drop Only