It cooling logicool ™ onrak, It cooling – Airedale OnRak 3kW 35kW User Manual
Page 13
IT Cooling
LogiCool
™ OnRak
IT Cooling
13
Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013
Cooling Performance LOR 6042U-C028-0 (N+1 configuration, Fans at 75%)
10
12
14
16
18
20
22
24
26
28
30
32
34
36
11
12
13
14
15
16
17
18
19
35°C SDT
40°C SDT
45°C SDT
(1) At the design chilled water temperature project a line until it intersects with the Server Discharge Temperature (SDT), read
off the cooling performance.
(e.g. 14°C projected up to 35°C SDT Line, reading across to 17.3kW.) All capacities based on water.
20
22
24
26
28
30
32
34
36
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
35°C SDT
40°C SDT
45°C SDT
(2) Take the capacity, project a line to intersect the server discharge temperature (SDT) again and you can then read off the
air off temperature. (E.g. 17.3kW projected up to 35°C SDT line, read across to air off temperature; 24.5°C).
All capacities based on water.