It cooling logicool ™ onrak, It cooling – Airedale OnRak 3kW 35kW User Manual

Page 13

background image

IT Cooling

LogiCool

™ OnRak

IT Cooling

13

Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013

Cooling Performance LOR 6042U-C028-0 (N+1 configuration, Fans at 75%)

10

12

14

16

18

20

22

24

26

28

30

32

34

36

11

12

13

14

15

16

17

18

19

35°C SDT

40°C SDT

45°C SDT


(1) At the design chilled water temperature project a line until it intersects with the Server Discharge Temperature (SDT), read
off the cooling performance.
(e.g. 14°C projected up to 35°C SDT Line, reading across to 17.3kW.) All capacities based on water.

20

22

24

26

28

30

32

34

36

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

35°C SDT

40°C SDT

45°C SDT

(2) Take the capacity, project a line to intersect the server discharge temperature (SDT) again and you can then read off the
air off temperature. (E.g. 17.3kW projected up to 35°C SDT line, read across to air off temperature; 24.5°C).
All capacities based on water.

Air O

ff T

e

m

pe

ratu

re

(°C)

C

ool

ing

P

e

rf

or

m

a

nce

(

k

W

)

Water Inlet Temperature °C (based on 6°C

T)

Cooling Performance (kW)