Setting for inrush current measurement, Setting for interval, Setting for referent current – KYORITSU 6310 Instruction Manual User Manual
Page 92
4.2.2 Measurement Setting (QUALITY-Inrush Current Measurement) KEW6310
4.51
KEW6310
Setting for Inrush Current Measurement
For the details of Inrush Current, refer to “11.4 Inrush Current Measurement” in this manual.
Setting Items
Interval
*1
set
interval time
Clamp sensor
: refer to Basic setting
A Range
: refer to Basic setting
Reference current
: select a Current Range of reference
Filter
: refer to Basic setting
Threshold value
: set in percentage against reference current
Hysteresis
: set in percentage against reference current
Trigger Point
: set a number of data save point prior to / following an event of trigger
* Selectable range for reference current (A/mA) is automatically displayed after selecting a Current
Range for 1ch at Basic setting.*1 Flicker measurement function is only available with ver.2.00 or later.
Setting for interval
* Default value (or after system reset) : 30 min
* Setting procedure is same to that for interval Setting for W/ Wh/ DEMAND.Refer to the procedure described in
the preceding pages.
Setting for referent current
Current Range
Selectable range
Resolution
100mA
10 ~ 100mA
0.1mA
500mA
50 ~ 500mA
0.1mA
1A
0.1 ~ 1A
0.001A
5A
0.5 ~ 5A
0.001A
10A 1
~
10A
0.01A
20A 2
~
20A
0.01A
50A 5
~
50A
0.01A
100A
10 ~ 100A
0.1A
200A
20 ~ 200A
0.1A
500A
50 ~ 500A
0.1A
1000A
100 ~ 1000A
1A
3000A
300 ~ 3000A
1A
* When “AUTO” is selected as a Current Range for A1, the max Range of Clamp
sensor is set automatically.
* Selectable range is within 10 to 100% of Current Range.