beautypg.com

Caution – HT instruments HT9012 User Manual

Page 4

background image

HT9012

EN - 3

1.2 BEFORE

USE

Always keep to the instructions contained in this manual:

CAUTION

Non compliance with the warnings and/or the instructions may damage the
tester and/or its components or injure the operator.

• Before changing the switch’s position, take off the clamp jaw from the tested conductor

or the electrical circuit in order to avoid any accident

• When the clamp is connected to the circuits to be tested, never touch unused terminals

• When testing resistors, do not add voltage. Although there is a protection circuit,

excessive voltage would cause malfunctioning

• Before measuring current, remove the voltage-resistance test leads

• When measuring current, any strong current near or close to the clamp jaw will affect

the accuracy

• When measuring current, always put the tested conductor in the middle of the clamp

jaw in order to obtain a more accurate reading

• If the reading value or the sign indication remains unchanged during the measurement,

check if the HOLD function is active

1.3 AFTER

USE

• Once the measurements are completed, turn the rotary switch to OFF

• If you expect not to use the clamp for a long time, remove the battery

1.4 MEASURING

(OVERVOLTAGE) CATEGORIES DEFINITIONS

The norm IEC/EN61010-1: Safety requirements for electrical equipment for measurement,
control and laboratory use, Part 1: General requirements, defines what measuring
category, usually called overvoltage category, is. On § 6.7.4: Measuring circuits, it says:

(OMISSIS)

circuits are divided into the following measurement categories:

Measurement category IV is for measurements performed at the source of the low-

voltage installation

Examples are electricity meters and measurements on primary overcurrent protection
devices and ripple control units

Measurement category III is for measurements performed in the building installation

Examples are measurements on distribution boards, circuit breakers, wiring, including
cables, bus-bars, junction boxes, switches, socket-outlets in the fixed installation, and
equipment for industrial use and some other equipment, for example, stationary
motors with permanent connection to fixed installation

Measurement category II is for measurements performed on circuits directly

connected to the low voltage installation

Examples are measurements on household appliances, portable tools and similar
equipment

Measurement category I is for measurements performed on circuits not directly

connected to MAINS

Examples are measurements on circuits not derived from MAINS, and specially
protected (internal) MAINS-derived circuits. In the latter case, transient stresses are
variable; for that reason, the norm requires that the transient withstand capability of the
equipment is made known to the user