SECTION 10 FUEL SUPPLY PUMP ELECTRICAL
INSTALLATION
CAUTION: HAZARD OF ELECTRICAL SHOCK
10.1 All wiring must comply with the National Electrical Code, State and Local
Ordinances, and be wired by a qualified electrician.
10.2 The electrical conductors to the fuel pump motor MUST be stranded 14 GA
minimum.
10.3 The electrical service connections for the fuel pump motor are made in the
electrical junction box on the back or side of the heater.
10.4 The pump motor MUST have a safety equipment ground from the main
electrical service, stranded 12 GA minimum.
10.5 The electrical conductors from the electrical junction box to the pump motor
must be within approved conduit.
10.6 Keep all electrical conductors and conduit away from the chimney
connector as well as any other hot surfaces. Refer to Section 18 Wiring
Diagram for color code, etc. Keep the power off until the heater is ready to
be started. Refer to Section 13 Start Up Procedure.