beautypg.com

Biamp CI-1 User Manual

Page 7

background image

7

REAR PANEL

Connections from External Devices for Fault Indications
B9)-)";,(;+,6-".()"5(4E,C)C"4/"."-,/=:)"Inputs are fully isolated from the CI­1 and LSI­16 internal circuits. The Isolated Ground 
provides a circuit return that is not directly connected to the CI­1 and LSI­16 Ground. 

These inputs allow the signaling of faults from external devices to the Vocia system 
so it may indicate and log faults that could affect emergency operation. These fault 
signals are typically derived from contact closures on external devices. For multiple 
devices (e.g. Multiple UPS units), fault contacts from each device may be ‘wired­OR’ 
connected (connected in parallel) to the fault input. UPS fault inputs are typically 
derived from UPS units used in the system (e.g. for backup powering of VA­8600 
units). PSU fault inputs are typically derived from battery­backed power supplies 
used to power parts of a Vocia system. EWS PSU fault inputs are derived from 
optional emergency microphones (EWS­x) to indicate loss of power supply. Ethernet 
fault inputs are derived from fault contacts of industrial Ethernet switches used in 
critical parts of a Vocia system.

All fault inputs are asserted by connecting the relevant pin to Isolated Ground. The UPS Fault, PSU Fault and EWS PSU Faults must be 
;4//);6)C"64"RN>"?9)/"/4/&.--)(6)C"),69)("GA"C,();6";4//);6,4/"4("69(4+=9"5+::&+5"()-,-64("JD.F,D+D"R7RSTL7"B9)"RN>"()3)()/;)"E4:6.=)"
output on the power supply connector may be used for this purpose. The Ethernet Fault input is pulled­up internally and does not need an 
external pull­up.

Connections to LSI­16
B9)-)";,(;+,6-".()"5(4E,C)C"4/"34+("JNL"K.;9";4//);64(":.G):",-"5()circuit connections may be made by directly connecting pin­for­pin to the vertically adjacent connector. Short interlinking cables are 
provided with the CI­1 for this purpose. Refer to the LSI­16 Operation Manual for the circuit functions of these connectors.

Note that the LSI­16 PSU Fault, Protection Fault and Path Fault outputs are connected to the CI­1 purely for the purpose of providing 
required monitoring resistors (these outputs are not otherwise used by the CI­1). If these outputs are required for remote fault indications, 
the relevant connections should be removed from the Monitored Outputs connector of the LSI­16. As described in the LSI­16 Operation 
Manual, and external monitoring resistor will be required if these circuits are so used.

Power Supply Connections
B9)-)";,(;+,6-".()"5(4E,C)C"4/"."-,/=:)"are provided for two 24V power supply circuits to drive the LSI­16. This facilitates 
standards compliance by providing a means of redundant connections.

Each power supply must be capable of 24V DC at 15Watts. The Ground 1 and 
Ground 2 connections are internally connected together and to system ground.  
The VRef connection may be used as a voltage source for pull­ups on required fault 
inputs. This output is current limited at 100mA.

Loss of power to either power supply input will result in the LSI­16 detecting a fault. 
If standards compliance is not required for an installation, a single power supply 
connection must be paralleled to the two power supply inputs to avoid generating  
a fault signal.

Connector

Label

Function

Isolated Ground

U

UPS Fault

P

PSU Fault

W

EWS PSU Fault

E

Ethernet Fault

Connector

Label

Function

 

 Ground 1

1

24 Volts DC Input 1

Ground 2

2

24 Volts DC Input 2

VRef

24 Volts Reference Out

This manual is related to the following products: