beautypg.com

Biamp CI-1 User Manual

Page 6

background image

6

REAR PANEL

There are four main interconnection paths to the rear panel:

!" $4//);6,4/-"64"69)"<()"C)6);6,4/"-A-6)D"J$%KLM

!" Connections from external devices for fault indications

!" Connections to the LSI­16

!" Power supply connections

Each of these connection paths has several circuits as detailed below.

Fire Detection System (CIE) Connections
B9)-)";,(;+,6-".()"5(4E,C)C"4/"6?4"Isolated Ground provides a circuit return that is not directly connected to the CI­1 
and LSI­16 Ground. 

#:.(D"%/5+6-"'"69(4+=9"N".()"-,=/.:-"3(4D"69)"<()"C)6);6,4/"-A-6)D7"B9)-)"-,=/.:-"
5:.;)"69)">4;,."-A-6)D",/64")D)(=)/;A"D4C)".;;4(C,/="64"69)";4/<=+(.6,4/"
determined for the input in Vocia software. The Alarm Reset Input cancels all active 
alarms in the system while the Alarm Silence Input maintains all active alarms but 
causes emergency messages to be silenced. The CI­1 provides the necessary 
terminating resistors for each input. Inputs are asserted by a positive transition 
to 12­24V with respect to the ‘Isolated Ground’ connection. This transition should 
preferably be derived from a dry contact closure to a remote 12V­24V source, or  
to the CI­1 24V Reference Out (see below).

B9)">4,;)"#:.(D"#;6,E)"4+65+6",-"5(4E,C)C"64"-,=/.:"64"69)"<()"C)6);6,4/"-A-6)D"69.6"
the Vocia system has been activated in emergency mode in response to an Alarm 
Input. A constant output denotes that an emergency message is playing. A pulsed 
output (1.25Hz) indicates that an alarm is active but emergency messages have 
been silenced.

B9)"O)/)(.:"P.+:6"Q+65+6",-"5(4E,C)C"64"-,=/.:"64"69)"<()"C)6);6,4/"-A-6)D"69.6"69)()"
is a fault in the Vocia system that could affect delivery of an emergency message.

The Voice Alarm Active and General Fault outputs pull low (to ground) when active. 
The outputs are monitored by the LSI­16 for open­circuit or short­circuit to ground or 
power supply and for over­voltage on the output pin (>35V DC). If incorrect conditions are detected a Fault is signaled. Output monitoring 
3.;,:,6.6)-";4D5:,./;)"?,69"E4,;)")E.;+.6,4/"-6./C.(C-7"P4("D4/,64(,/="5+(54-)-".":4.C"JD.F,D+D"RRSTL"D+-6"G)";4//);6)C"G)6?))/"
each output and a positive voltage source referenced to the LSI­16 Ground, at the far end of the connection to the CIE (i.e. at the CIE).  
#/"0KU",/C,;.64(";4//);6)C"69(4+=9"."()-,-64("64"."54-,6,E)"E4:6.=)".6"69)"$%K"?,::"-+3<;)".-"."D4/,64(,/=":4.C7"

V46)"69.6"69)"01%&'2"5(4E,C)-"."'W>"-4+(;)".6"69)"X'W>"Q+6Y"6)(D,/.:"4/"69)"01%&'27"Q+65+6-"D.A"G)"5+::)C"+5"64"69,-"-4+(;)M"94?)E)("69)"
total current drawn from the source must not exceed 100mA. If an external voltage source is used for the outputs, it must not exceed 35V 
DC and in addition to the output loads, must also be connected to the LSI­16 ‘External Supply Over­voltage Monitor’ input (refer to LSI­16 
User Manual) for monitoring purposes. Due to monitoring constraints, it is not possible to use both the LSI­16 internal 10V source and an 
external source. 

Connector

Label

Function

Isolated Ground

A1

Alarm 1 Input from CIE

A2

Alarm 2 Input from CIE

A3

Alarm 3 Input from CIE

A4

Alarm 4 Input from CIE

Rs

Alarm Reset Input from CIE

Si

Alarm Silence Input from CIE

 

Ground

VA

Voice Alarm Active Output to CIE

GF

General Fault Output to CIE

This manual is related to the following products: