beautypg.com

Sealing, Cooling equipment, Air handler equipped with refrigerant coil (dx) – AAON M1-011 User Manual

Page 18

background image

18

Note that a heat wheel module will have a 100 series
number identifying it, but will span both tiers also
utilizing a 200 series space, and effectively “skipping”
one of the top-tiered numbers.

If, for any reason, you are unable to identify any
module, or its position in the final assembly, then
consult the salesperson or project engineer.

Table 4.1, Module Code Chart

Code

Description

BBA

Small Blank Box

BBB

Large Blank Box

CLB

Cooling

Coil

CLC

Cooling Coil/Hot Gas Reheat Coil

CLD

Electric Heat/Hot Water Coil

CLE

Electric

Heat

CLF

Hot Water/Cooling Coil

CLG

Electric Heat/Cooling Coil

CLH

Electric Heat/Cooling Coil/Hot Gas Reheat Coil

CLI

Cooling or Heating w/ Face Bypass

CLJ

Hot Water/Cooling Coil/Hot Gas Reheat Coil

CLK

Vertical Cooling Coil

CLL

Cooling and Heating w/ Face Bypass

FTA

Small Flat Filter

FTB

Angled

Filter

FTC

Cartridge

Filter

FTD

Bag

Filter

FTF

Large

Flat

Filter

HRA Energy

Recovery

Wheel

MBA

Vertical Damper Mixing Box

MBB

Horizontal Damper (top) Mixing Box

MBC Horizontal

(bottom)/Vertical Damper Mixing Box

MBD

Vertical Damper/Filter Mixing Box

MBE

Horizontal Damper (top)/Filter Mixing Box

MBF

Horizontal Damper (bottom) Mixing Box

MBG

Filter Mixing Box (no damper)

MBH Vertical/Horizontal

(top) Damper Mixing Box

MBI

Filter/Horizontal (bottom) Damper Mixing Box

MBJ

Vertical/Horizontal (top) Damper/Filter Mixing Box

MBK

Vertical/Horizontal (bottom) Damper/Filter Mixing Box

PEA

Power

Exhaust

PHA

Electric

Heat

PHB

Hot Water Coil

PHC Filter/Hot

Water

Coil

PHD Filter/Electric

Heat

RFA

Return

Fan

RHC

Hot Gas Reheat Coil

SFA

Supply

Fan

SFB

Vertical

Supply

Fan

SFC

Supply Fan with Top Discharge

TRA

Control

Box


After identifying modules and determining module
arrangement, you can begin connecting the modules.

Modules are to be connected with nuts and bolts that
are shipped with the unit. Bolt holes are located inside
the module frames near the corners, and in the base
rail below the outside bottom corners of the module
(due to various design criteria, some modules may
have additional bolt holes along the inside of the

module top, and should be used if present). Align
modules, and insert bolts through the bolt holes of two
adjacent modules, and secure with nuts to pull the two
modules together tightly. Every bolt hole must be
used to ensure a tight seal between modules, and a
structurally stable assembly.








Figure 4.4, Bolted Base Rail



Sealing

It is very important to keep outside air from infiltrating
the unit cabinet. Seal all piping penetrations with
Armaflex, Permagum, or other suitable sealant. Also
seal around drain connections, electrical connections,
and all other inlets where air may enter the cabinet.
This is especially important when the unit is installed in
an unconditioned area.

Cooling Equipment

Air Handler Equipped with Refrigerant Coil (DX)


This section is not intended to provide all the
information required by the designer or installer of the
refrigerant piping between the condensing units and
the air handler. The appropriate sections of the
ASHRAE Guide and the ASME standards should be
used for final information. Acceptable system design
and installation will include consideration as follows:

NOTE

All nuts, bolts, and gasketing required for assembly
are packaged and shipped with unassembled unit
orders.

This manual is related to the following products: