SYSTEM WIRING

Page

7 - 29

7

TS-IEM Wiring (T2)

Two AC/DC interface terminals are included for up to 8 inputs or outputs per
TS-IEM I/O module. See Figure 7-13d for a typical wiring diagram.

ELECTRICAL DANGER

External power sources are present at the

TS-IEM module avoid Electrical Shock Hazards, which may cause
injury or death. Before working on the these circuits:

Turn off all power to the TS-2001 system — at the electrical power panel.

Turn off all external power sources that are wired to the TS-IEM
module(s) and verify that no voltage is present !

DO NOT install or remove I/O modules, fuses, or wiring with power
applied !

DO NOT wire any unused module terminals

Recommended Wire

Use a minimum of 18 AWG (1 mm), type TFFN, THWN, or THHN wire.

Wire only one input/output to an interface terminal-set.

Wire each input or output module as shown in Figure 7-13d.

For each TS-IEM channel, Record the Module Type, Power Source, and Circuit
Description in TABLE 7-6.

At each interface terminal-set: clearly mark the wiring with the external power
source !

After TS-IEM Wiring — Steps

1) Reinstall all safety shields and covers.
2) Make sure all work is finished and all personnel are clear before powering up
3) Program the TS-2001 for these I/O modules as installed and recorded in

TABLE 7-6.

4) Test each input or output for proper operation.