TABLE 7-2

230 VAC Line Power Wire Connection List:

Electrical Panel

No. Conductors, Color (Gauge)

Circuit

Console Terminal

10 Amp C.B. (Load) 1 Black wire,16 AWG (1.3 mm) min.

230 VAC Power

**

J17 - L1

Ground Bus

1 White wire,16 AWG (1.3 mm) min.

Neutral

J17 - L2 (NEUT)

Ground Bus

1 Green wire,16 AWG (1.3 mm) min.

Ground

J17 - GND

Ground Bus

1

*

Green wire,12 AWG (2.1 mm) min.

Safety Ground

J17 - SAFETY GND

*

= two (2) Safety Ground wires may be required in some locations (check your Local and

National Electric Codes).

** = This is Euro-standard 230 VAC power configuration – L2 is Neutral. The Model/SN

label will indicate 230 VAC.

NOTE

NOTE

Figure 7-3b.

230 VAC Power and I.S. Ground Wiring

ELECTRICAL POWER PANEL

(SHOWN WITH COVER REMOVED)

O F F

O F F

M A I N

20

OF

F

3 4

OF

F

15

20

OF

F

1 2

OF

F

10

- CIRCUIT ASSIGNMENT LABEL -

ELECTRICAL POWER PANEL DOOR

BACK SIDE VIEW

A

L I G H T S 1 0 A

C O O L E R 1 5 A

1 1

1 2

T A N K 1 0 A

S E N T I N E L

1 5

1 6

1 3

1 4

P U M P # 1 2 0 A

7

8

9

1 0

5

6

1

2

3

4

B

N

REDUNDANT
INTRINSIC SAFETY
GROUND
GREEN WIRE, 12 AWG
(2.1 mm) MIN.
- REQUIRED IN
SOME AREAS -

NOTE:
SOME CONSOLES
MAY HAVE TEXT
DESIGNATIONS THAT
DIFFER SLIGHTLY
FROM WHAT
IS SHOWN HERE.

CU EARTH
GROUND ROD

SAF

E

T

Y

GN

D

INTRINSIC SAFETY GROUND
(GREEN WIRE, 12 AWG (2.1 mm) MIN.)

NEUTRAL
BUS

GREEN (GND-GROUND) WIRE, 16 GA. (1.3 mm) MIN.

WHITE (L2-NEUTRAL) WIRE, 16 GA. (1.3 mm) MIN.

TANK SENTINEL
CONSOLE

PO

W

E

R

GN

D

L1

NE

UT

BLACK (L1-LINE) WIRE, 16 GA. (1.3 mm) MIN.

1 6

1 5

10

OF

F

GROUND
BUS

Enclosure

Nut

Lock Washer

Earth Ground Conductor

Cup Washer

Stud: #8 threaded post

The installer is to connect the Earth Ground
Conductor to the most convenient ground
terminal as long as it meets local and national
codes. If the ground stud is to be used the
installer shall follow the proper stacking
configuration shown in figure 7-3c The earth
ground conductor must be 12 AWG (2.1 mm)
or larger.

NOTE

Figure 7-3c.

Ground Stud