In this mode both pumps can work in different modes, switching between
pumps is made by NMTC module.
- Alternating mode [factory set] - One pump works, while the other one is
in standby. Pumps automatically switch on and in to standby every 24
hours, or when an error occurs on one pump.
- Reserve mode - One pump is always on, while the other one is in standby.
If an error occurs, then the reserve pump will turn on. This mode is turned
on, so that you put the pump that you want to be in standby, to standby by
holding
key for 5 seconds.
- Combined mode – both pumps work with the same head in constant
pressure mode. This mode is used when there is a need for a flow that a
single pump can't reach. When the limit of the first pump is reached, then
the other one will turn on supply the needed power to reach that flow.
This mode is activated, so that you set the same constant pressure head
on both pumps.
NMTD SMART
In this mode the pumps can work in different modes. The user takes care of
switching on and off of the pumps.
- Reserve mode - One pump works, while the other one is in standby. It is
recommended that the reserve pump is turned on at least once a month.
- Combined mode – Both pumps work, regardless of each other. Pumps
need to be set at the same constant speed.
6.
Technical specifications
NMT(D) SMART (C)
Pump type
xx/120-xxx
xx/100-xxx
xx/80-xxx
xx/60-xxx
xx/40-xxx
Power P
1
10-180W
10-180W
10-140W
10-90W
10-60W
Rated current In
0,1-1,55A
0,1-1,5A
0,1-1,15A
0,1-0,75A
0,1-0,5A
Power supply
1~230V, 50Hz
Motor protection
External protection is not necessary
Protection class
IP44
Insulation class
F
Relative humidity
max 95%
Ambient temperature
0-40°C
Medium temperature
2-110°C
System pressure
up to 1 MPa (10 bar)