1 rdc2 generator set/ transfer switch controller, 2 controls and indicators – Kohler Power Systems 14/20RESA User Manual
Page 29
TP-6804 12/11
29
Section 3 RDC2 Controller Operation
Section 3 RDC2 Controller Operation
3.1 RDC2 Generator Set/ Transfer
Switch Controller
Model RESA generator sets are equipped with the
RDC2 generator set/transfer switch controller.
Model RESAL generator sets are equipped with the
DC2 controller.
See Section 4 for DC2 controller
operation information.
The RDC2 controls the following power system
components:
D
Model 14RESA or 20RESA generator set
D
Model RXT Automatic Transfer Switch (ATS)
D
Load Control Module (LCM)
D
Programmable Interface Module (PIM)
The RDC2 controller features include:
D
Two-line x 16 character backlit digital display with
adjustable contrast
D
OFF, AUTO, and RUN generator set master control
buttons
D
Generator set status indicating LEDs (OFF, AUTO,
RUN)
D
Up, Down, and Select buttons for navigation through
menus and adjustments
D
Power system indicator LEDs to show utility and
generator source status, and to show which source
(utility or generator) is supplying power to the load
3.2 Controls and Indicators
Figure 3-1 illustrates the RDC2 controller.
See
Figure 3-2 for details of the controller’s user interface.
1. User Interface; see Figure 3-2
2. Service access (see Section 6.4)
1
2
GM77569
Figure 3-1
RDC2 Controls and Indicators
1. 2-line LCD display
2. Up button
3. Select button
4. Down button
5. RUN button and LED
6. Generator power available LED*
7. Building on generator power LED*
8. Building on utility power LED*
9. Utility power available LED*
10. OFF button and LED
11. AUTO button and LED
* These LEDs operate only if a Model RXT transfer switch is
connected.
1
10
3
2
5
11
4
GM77569
6
7
8
9
Figure 3-2
RDC2 User Interface