Terminal assignment, 1 terminal assignment ex e, Version 2.00 – I-Data POLARIS Panel PC 19.1" User Manual
Page 16

User manual
POLARIS
Panel PC 19.1'' and Panel PC 15''
Version 2.00
Page 16 of 46
E_BMS790_POLARIS_PanelPC_19+15_Rev1.doc
•
User manual for POLARIS Panel PC 19.1" and 15"
•
Revision 1 / Status: January, 3
rd
, 2006
•
Technical data subject to change
3. Terminal
assignment
3.1
Terminal assignment Ex e
Terminal Interface
Signal
Remarks
X10
Supply
L
AC 230 V ± 10 %
X11 Supply
N
Neutral
X12 Supply
PE
Protective
earth
Configuration of RS422 interface of Ethernet 10BaseT
X13 Ethernet
RxD
+
10BaseT
Receive
positive
X14 Ethernet
RxD
-
10BaseT
Receive
negative
X15 Ethernet
TxD
+
10BaseT
Transmit
positive
X16 Ethernet
TxD
-
10BaseT
Transmit
negative
Configuration of RS422 interface
X17
Jumper between terminal X17 and X18 for
X18
Termination On/Off
activation of the terminator resistors
X19
Interface COM 1
TxD B (TxD+)
Transmission cable
Input
X20
Interface COM 1
TxD A (TxD-)
Transmission cable
Input
X21
Interface COM 1
RxD B (RxD+)
Receiving cable
Input
X22
Interface COM 1
RxD A (RxD-)
Receiving cable
Input
X23
Interface COM 1
TxD B (TxD+)
Transmission cable
Output
X24
Interface COM 1
TxD A (TxD-)
Transmission cable
Output
X25
Interface COM 1
RxD B (RxD+)
Receiving cable
Output
X26
Interface COM 1
RxD A (RxD-)
Receiving cable
Output
When interface used with PROFIBUS-DP interface in place of RS422:
Configuration of PROFIBUS-DP interface
Terminal Interface
Signal
Remarks
X17
GND PROFIBUS
PE
Additional ground
X18 not
connected
N.C.
X19
Interface COM 1
Termination B2
Bridge for terminating network
(B1-B2)
X20
Interface COM 1
Termination A2
Bridge for terminating network
(A1-A2)
X21
Interface COM 1
Termination B1
Bridge for terminating network
(B1-B2)
X22
Interface COM 1
Termination A1
Bridge for terminating network
(A1-A2)
X23
Interface COM 1
Out B
Signal B
Output
X24
Interface COM 1
Out A
Signal A
Output
X25
Interface COM 1
In B
Signal B
Input
X26
Interface COM 1
In A
Signal A
Input