IBM UPS750TLV User Manual
Page 14
10
N
OTE
: S
ETTINGS ARE MADE THROUGH THE SUPPLIED
P
OWER
C
HUTE SOFTWARE OR
O
PTIONAL
S
MART
S
LOT ACCESSORY CARDS
. R
EFER TO THE SOFTWARE HELP GUIDES FOR DETAILS
.
F
UNCTION
F
ACTORY
D
EFAULT
U
SER
S
ELECTABLE
C
HOICES
D
ESCRIPTION
High Transfer Point
750TLV, 1000TLV
and 1500TLV mod-
els:127AC
750THV, 1000THV
and 1500THV mod-
els:253VAC
750TLV, 1000TLV
and 1500TLV models:
127, 130, 133, 136VAC
750THV, 1000THV
and 1500THV models:
253, 257, 261, 265VAC
If the utility voltage is usually high and the
connected equipment is specified to operate
with input voltages this high, set the high
transfer point higher to avoid unnecessary
battery usage.
Low Transfer Point
750TLV, 1000TLV
and 1500TLV mod-
els:106VAC
750THV, 1000THV
and 1500THV mod-
els:208VAC
750TLV, 1000TLV
and 1500TLV models:
97, 100, 103, 106VAC
750THV, 1000THV
and 1500THV models:
196, 200, 204, 208VAC
If the utility voltage is usually low and the
connected equipment is specified to operate
with input voltages this low, set the low
transfer point lower.