beautypg.com

Warning – Goodman Mfg GKS9 User Manual

Page 27

background image

27

B

OTTOM

R

ETURN

A

IR

O

PENING

[U

PFLOW

M

ODELS

]

The bottom return air opening on upflow models utilizes a “lance
and cut” method to remove sheet metal from the duct opening in
the base pan. To remove, simply press out the lanced sections by
hand to expose the metal strips retaining the sheet metal over the
duct opening. Using tin snips, cut the metal strips and remove the
sheet metal to free the duct flanges. Using the scribe line along the
duct flange as a guide, unfold the duct flanges around the perim-
eter of the opening using a pair of seamer pliers or seamer tongs.
NOTE: Airflow area will be reduced by approximately 18% if duct
flanges are not unfolded. This could cause performance issues
and noise issues.

E

DGES

OF

SHEET

METAL

HOLES

MAY

BE

SHARP

. U

SE

GLOVES

AS

A

PRECAUTION

WHEN

REMOVING

SHEET

METAL

FROM

DUCT

OPENING

.

WARNING

CUT FOUR CORNERS
AFTER REMOVING SHEET
METAL

CUT USING TIN SNIPS

PRESS OUT BY HAND

SCRIBE LINES OUTLINING
DUCT FLANGES

Duct Flange Cut Outs

When the furnace is used in connection with a cooling unit, the
furnace should be installed in parallel with or on the upstream side
of the cooling unit to avoid condensation in the heating element.
With a parallel flow arrangement, the dampers or other means
used to control the flow of air must be adequate to prevent chilled
air from entering the furnace and, if manually operated, must be
equipped with means to prevent operation of either unit unless the
damper is in the full heat or cool position.

When the furnace is installed without a cooling coil, it is recom-
mended that a removable access panel be provided in the outlet
air duct. This opening shall be accessible when the furnace is
installed and shall be of such a size that the heat exchanger can be
viewed for visual light inspection or such that a sampling probe can
be inserted into the airstream. The access panel must be made to
prevent air leaks when the furnace is in operation.

When the furnace is heating, the temperature of the return air enter-
ing the furnace must be between 55°F and 100°F.

F

ILTERS

- R

EAD

T

HIS

S

ECTION

B

EFORE

I

NSTALLING

T

HE

R

ETURN

A

IR

D

UCTWORK

Filters must be used with this furnace. Discuss filter maintenance
with the building owner. Filters do not ship with this furnace, but
must be provided by the installer. Filters must comply with UL900
or CAN/ULCS111 standards. If the furnace is installed without fil-
ters, the warranty will be voided.

On upflow units, guide dimples locate the side return cutout
locations. Use a straight edge to scribe lines connecting the
dimples. Cut out the opening on these lines. NOTE: An
undersized opening will cause reduced airflow.

Refer to Minimum Filter Area tables to determine filter area require-
ments.

600

800

1000

1200

1400

1600

2000

0453_XA

188*

192

240

288

---

---

---

0703_XA

---

282*

282*

282*

336

---

---

0704_XA

---

---

260*

260*

336

384

---

0904_XA

---

---

376*

376*

376*

384

---

0905_XA

---

---

---

376*

376*

384

480

115_XA

---

---

---

470*

470*

470*

480

Input

__Ai

rf

lo

w

COOLING AIRFLOW REQUIREMENT (CFM)

*Minimum filter area dictated by heating airflow requirement.

Permanent Minimum Filter Area (sq. in)

[Based on a 600 ft/min filter face velocity]

600

800

1000

1200

1400

1600

2000

0453_XA

376*

384

480

576

---

---

---

0703_XA

---

564*

564*

564*

672

---

---

0704_XA

---

---

564*

564*

672

768

---

0904_XA

---

---

752*

752*

752*

768

---

0905_XA

---

---

---

752*

752*

768

800

1155_XA

---

---

---

940*

940*

940*

800

In

p

u

t_

_

A

irflo

w

COOLING AIRFLOW REQUIREMENT (CFM)

*Minimum filter area dictated by heating airflow requirement.

Disposable Minimum Filter area (sq. in)

[Based on 300 ft/min filter face velocity]

U

PRIGHT

I

NSTALLATIONS

Depending on the installation and/or customer preference, differ-
ing filter arrangements can be applied. Filters can be installed in
the central return register or a side panel external filter rack kit
(upflows). As an alternative a media air filter or electronic air cleaner
can be used as the requested filter.

The following figure shows possible filter locations.

FI

LT

E

R

AIR FLOW

CENTRAL

RETURN

GRILLE

FI

L

T

E

R

SIDE RETURN

EXTERNAL FILTER

RACK KIT

(EITHER SIDE)

Possible Upright Upflow

Filter Locations