1- 4
Function Mode
Code
Function name
SJ300 Setting range
Initial data
-FE/-FU/-F
Note
A061
1
s t
frequency maximum limiter
0.00, 1
s t
frequency lower limitter - maximum frequency(Hz)
0.00
A261
2
nd
frequency maximum limiter
0.00, 2
nd
frequency lower limiter-2
nd
setting maximum frequency(Hz)
0.00
A062
1
s t
frequency minimum limiter
0.00, start frequency-maximum frequency(Hz)
0.00
A262
2
nd
frequency minimum limiter
0.00, start frequency-2
nd
setting maximum frequency(Hz)
0.00
A063
Jump frequency1
0.00-99.99/100.0-400.0(Hz)
0.00
A064
Jump frequency Width 1
0.00-10.00(Hz)
0.50
A065
Jump frequency2
0.00-99.99/100.0-400.0(Hz)
0.00
A066
Jump frequency Width 2
0.00-10.00(Hz)
0.50
A067
Jump frequency3
0.00-99.99/100.0-400.0(Hz)
0.00
A068
Jump frequency Width 3
0.00-10.00(Hz)
0.50
A069
Acceleration stop frequency
0.00-99.99/100.0-400.0(Hz)
0.00
A070
Acceleration stop time
0.00-60.0(s)
0.0
A071
PID selection
00(invalid)/01(valid)
00
A072
PID-P gain
0.2-5.0
1.0
A073
PID-I gain
0.0-3600.(s)
1.0
A074
PID-D gain
0.00-100.0(s)
0.00
A075
PID scale
0.01-99.99(%)
1.00
A076
PID feedback selection
00(feedback : OI)/01(feedback : O)
00
A081
AVR selection
00(ON always)/01(OFF always)/02(OFF on decelerating)
00/00/02
A082
Motor voltage selection
200/215/220/230/240, 380/400/415/440/460/480
(230/400)/
(230/460)/
(200/400)
A085
Operation mode selection
00(normal operation)/01(energy-saving operation)/02(Fuzzy)
00
A086
Energy-saving response-
accuracy adjustment
0.0-100.0
50.0
A092
Acceleration time2
0.01-99.99/100.0-999.9/1000.-3600.(s)
15.00
A292
Acceleration time2(2
nd
motor)
0.01-99.99/100.0-999.9/1000.-3600.(s)
15.00
A392
Acceleration time2(3
rd
motor)
0.01-99.99/100.0-999.9/1000.-3600.(s)
15.00
A093
Deceleration time2
0.01-99.99/100.0-999.9/1000.-3600.(s)
15.00
A293
Deceleration time2(2
nd
motor)
0.01-99.99/100.0-999.9/1000.-3600.(s)
15.00
A393
Deceleration time2(3
rd
motor)
0.01-99.99/100.0-999.9/1000.-3600.(s)
15.00
A094
2
nd
stage adjustable selection
00(change with 2CH terminal)/01(change with setting)
00
A294
2
nd
stage adjustable
selection(2
nd
motor)
00(change with 2CH terminal)/01(change with setting)
00
A095
2
nd
acceleration frequency
0.00-99.99/100.0-400.0(Hz)
0.00
A295
2
nd
acceleration
frequency(2
nd
motor)
0.00-99.99/100.0-400.0(Hz)
0.00
A096
2
nd
deceleration frequency
0.00-99.99/100.0-400.0(Hz)
0.00
A296
2
nd
deceleration frequency
(2
nd
motor)
0.00-99.99/100.0-400.0(Hz)
0.00
A097
Acceleration pattern selection
00(straight line)/01(S-curve)/02(U-curve)/03(reverse U-curve)
00
A098
Deceleration pattern selection
00(straight line)/01(S-curve)/02(U-curve)/03(reverse U-curve)
00
A101
OI start
0.00-99.99/100.0-400.0(Hz)
0.00
A102
OI end
0.00-99.99/100.0-400.0(Hz)
0.00
A103
OI start rate
0.-100. (%)
20.
A104
OI end rate
0.-100. (%)
100.
A105
OI start selection
00(external start frequency)/01(0Hz)
01
A111
O2 start
-400.--100./-99.9-0.00-99.9/100.-400.(Hz)
0.00
A112
O2 end
-400.--100./-99.9-0.00-99.9/100.-400.(Hz)
0.00
A113
O2 start rate
-100. - 100. (%)
-100.
A114
O2 end rate
-100. - 100. (%)
100.
A131
Acceleration curve constant
01(small swelling)-10(large swelling)
02
A132
Deceleration curve constant
01(small swelling-10(large swelling)
02
b001
Retry selection
00(trip)/01(0Hz start)/02(start after equal frequency)/
03(trip after equaling frequency and deceleration stop)
00
b002
Allowable under-voltage power
failure time
0.3-1.0(s)
1.0
b003
Retry wait time
0.3-100.(s)
1.0
b004
Instantaneous power failure/
under-voltage trip during stop
00(invalid/01(valid)/02(invalid during stop and deceleration by stop
command)
00
b005
Instantaneous power failure/
under-voltage retry time
selection
00(16 times)/01(free)
00
b006
Open-phase selection
00(invalid)/01(valid)
00
b007
Frequency setting to match
0.00-99.99/100.0-400.0(Hz)
0.00
Upper and lower
limiter,jump
frequency
PID control
AVR
Operation mode/ adjustable function
External frequency
adjustment
Accel,
Decel
Instantaneous power failure
restart