Function mode – Hitachi SJ300 User Manual
Page 10
1- 7
Function mode
Code
Function name
SJ300 Setting range
Initial data
-FE/-FU/-F
Note
b034
RUN time/Power ON time level
0.-9999./1000-6553(10000-65530)hr
0.
b035
Operation direction restrict
00(Reverse is valid)/01(Only forward)/02(Only reverse)
00
b036
Start reduced voltage
00(Start reduced voltage time small)-06(Start reduced voltage time large)
06
b037
Display selection
00(all display)/01(each function display)/02(User setting / main setting)
00
b040
Torque limit mode selection
00(4 quadrant mode)/01(Terminal operation)/
02(Analog input)/03(Option1)/04(Option2)
00
b041
Torque limit level 1 setting
(Forward-driving at
4 quadrant mode)
0.-200.(%)/no(Invalid) <0.-180.(%)/no(Invalid)>
150.
b042
Torque limit level 2 setting
(Reverse-regenerating at
4 quadrant mode)
0.-200.(%)/no(Invalid) <0.-180.(%)/no(Invalid)>
150.
b043
Torque limit level 3 setting
(Reverse-driving at
4 quadrant mode)
0.-200.(%)/no(Invalid) <0.-180.(%)/no(Invalid)>
150.
b044
Torque limit level 4 setting
(Forward-regenerating at
4 quadrant mode)
0.-200.(%)/no(Invalid) <0.-180.(%)/no(Invalid)>
150.
b045
Torque LAD-STOP selection
00(Invalid)/01(Valid)
00
b046
Reverse run prevention
selection
00(Invalid)/01(Valid)
00
b050
Selection of non-stop
function at instantaneous
power failure
00(Invalid)/01(Valid)
00
b051
Start voltage of non-stop
function setting
0.0-1000.(V)
0.0
b052
OV LAD-STOP level of non-
stop function setting
0.0-1000.(V)
0.0
b053
Deceleration time of non-
stop function setting
0.01-99.99/100.0-999.9/1000.-3600.(s)
1.00
b054
Deceleration frequency widt h
of non-stop function setting
0.00-10.00(Hz)
0.00
b080
AM adjustment
0. - 255.
180
b081
FM adjustment
0. - 255.
60
b082
Start frequency adjustment
0.10-9.99(Hz)
0.50
b083
Carrier frequency setting
0.5-15.0(kHz) Derating enable, <0-10kHz>
5.0 <3.0>
b084
Initialize mode
00(Trip history clear)/01(Data initialization)/
02(Trip history clear + data initialization)
00
b085
Country code for initialization
00(Interior)/01(EC)/02(USA)
01/02/00
b086
Frequency scalar conversion
factor
0.1-99.9
1.0
b087
STOP key enable
00(valid)/01(invalid)
00
b088
Resume on FRS cancellation
mode
00(0Hz start)/01(Start f-equaling)
00
b090
BRD usage ratio
0.0-100.0(%)
0.0
b091
Stop mode selection
00(deceleration stop)/01(Free-run stop)
00
b092
Cooling fan control
00(Always ON)/
01(ON during run, After power ON, then for 5 minutes on stop is implied.)
00
b095
BRD selection
00(invalid)/01(valid
00
b096
BRD ON level
330-380/660-760(V)
360/720
b098
Thermistor selection
00(invalid)/01(Positive temperature coefficient enable)/02 (NTC enable)
00
b099
Thermistor error level
0. - 9999. ( ohm)
3000.
b120
Braking control selection
00(Invalid)/01(valid)
00
b121
Waiting time for releasing
braking conformation
0.00-5.00(s)
0.00
b122
Waiting time for acceleration
0.00-5.00(s)
0.00
b123
Waiting time for stop
0.00-5.00(s)
0.00
b124
Waiting time for signal
conformation
0.00-5.00(s)
0.00
b125
Releasing frequency
0.00-99.99/100.0-400.0(Hz)
0.00
b126
Releasing current
0.00*rated current-2.00*rated current(A)
Rated
current of
inverter
C091
Debug mode selection
00(No display)/01(Display)
00
C101
UP/DWN selection
00(No frequency data)/01(Keep frequency data)
00
C102
Reset selection
00(Trip cancel during ON)/01(Trip cancel during OFF)/
02(Valid only during trip
00
C103
Reset f frequency matching
selection
00(0Hz start)/01(Start f-equaling)
00
C111
Overload
advance
notice
level
0.0-2.0*rated current(A)
Inverter
rated
current
C121
O zero adjustment
0.-9999./1000-6553(10000-65530)
Set on
forwarding
C122
OI zero adjustment
0.-9999./1000-6553(10000-65530)
Set on
forwarding
C123
O2 zero adjustment
0.-9999./1000-6553(10000-65530)
Set on
forwarding
(Note) < > indicate the setting range of 75 to 150kW
The others