Function mode – Hitachi SJ300 User Manual
Page 12

1- 9
Function mode
Code
Function name
SJ300 Setting range
Initial data
-FE/-FU/-F
Note
P001
Option1 operation selection
on error
00(TRP)/01(RUN)
00
P002
Option2 operation selection
on error
00(TRP)/01(RUN)
00
P010
Feed-back option selection
00(Invalid)/01(Valid)
00
P011
Encoder pulse number
setting
128.-9999./1000-6500(10000-65000) (pulse)
1024
P012
Control mode selection
00(ASR mode)/01(APR mode)
00
P013
Pulse train input mode
selection
00(Mode 0)/01(Mode 1)/02(Mode 2)/03(Mode 3)
00
P014
Orientation stop position
setting
0.-4095.
0.
P015
Orientation speed setting
0.00-99.99/100.0-120.0(Hz)
5.00
P016
Orientation direction
selection
00(Forward)/01(Reverse)
00
P017
Orientation completion range
setting
0.-9999./1000(10000) (pulse)
5
P018
Orientation completion delay
time setting
0.00-9.99(s)
0.00
P019
Electronic gear position
selection
00(Feedback)/01(Reference)
00
P020
Electronic gear numerator of
ratio setting
0.-9999.
1.
P021
Electronic gear denominator
of ratio setting
0.-9999.
1.
P022
Position control feed-forward
gain setting
0.00-99.99/100.0-655.3
0.00
P023
Position control loop gain
setting
0.00-99.99/100.0
0.50
P025
Compensation of secondary
resistor selection
00(Invalid)/01(Valid)
00
P026
Over-speed detect level
setting
0.00-99.99/100.0-150.0(%)
135.0
P027
Speed-error over detect level
setting
0.00-99.99/100.0-120.0(Hz)
7.50
P031
Digital input option input
mode selection ( Acc/Dec)
00(operator)/01(option1)/02(option2)
00
P032
Stop position setting for
orientation input mode
selection
00(operator)/01(option1)/02(option2)
00
P044
DeviceNet running order of
monitoring timer setting
0.00-99.99s
1.00
P045
Setting in action of abnormal
communication
00(trip)/01(trip after deceleration stop)/02(invalid)/
03(free-run)04(deceleration stop)
0.
P046
Output assemble instance
Number setting
20,21,100
21
P047
Input assemble instance
Number setting
70,71,101
71
P048
Detect of idol mode for
motion setting
00(trip)/01(trip after deceleration stop)/02(invalid)/
03(free-run)04(deceleration stop)
01
P049
Pole setting of rotation speed
0-38(even only)
0
U001
User1 selection
no/d001-P049 <-P032>
no
U002
User2 selection
no/d001-P049 <-P032>
no
U003
User3 selection
no/d001-P049 <-P032>
no
U004
User4 selection
no/d001-P049 <-P032>
no
U005
User5 selection
no/d001-P049 <-P032>
no
U006
User6 selection
no/d001-P049 <-P032>
no
U007
User7 selection
no/d001-P049 <-P032>
no
U008
User8 selection
no/d001-P049 <-P032>
no
U009
User9 selection
no/d001-P049 <-P032>
no
U010
User10 selection
no/d001-P049 <-P032>
no
U011
User11 selection
no/d001-P049 <-P032>
no
U012
User12 selection
no/d001-P049 <-P032>
no
(Note 1) P044-P049 are displayed on a 0.4-55kW model.
User selection
Option