beautypg.com

A. chimney requirements, Table 8.1 – Hearth and Home Technologies A42C User Manual

Page 25

background image

25

A. Chimney Requirements

Measure vertical distances from the base of the fi replace
as shown in Figure 8.2.

20 ft (6.10 m) max.
pipe between an
offset & return

Ceiling firestop

35 ft (10.7 m)

max. straight

unsupported

chimney height

16.5 ft (5.03 m) min. height/single offset-return

20 ft. (6.10 m) min. height/double offset-return

90 ft (27.4 m) max. height

6 ft (1.83 m) max.
unsupported chimney
above roof

41-1/4 in.

(1048 mm)

Effective

Height

Figure 8.2 Chimney Requirements

Table 8.1

• Minimum overall straight height

16.5 ft

(5.03 m)

• Minimum height with offset/return

16.5 ft

(5.03 m)

• Maximum height

90 ft

(27.43 m)

• Maximum chimney length between an offset

and return

20 ft

(6.1 m)

• Maximum distance between chimney

stabilizers

35 ft

(10.67 m)

• Double offset/return minimum height

20 ft

(6.1 m)

• Maximum unsupported chimney length

between the offset and return

6 ft

(1.83 m)

• Maximum unsupported chimney height above

the fi replace

35 ft

(10.67 m)

• Maximum unsupported chimney above roof

6 ft

(1.83 m)

WARNING! Risk of Fire! You must maintain 2 in. (51
mm) air space clearance to insulation and other combus-
tible materials around the chimney system. Failure to do
so may cause overheating and fi re.

Determine the chimney components needed to complete
your particular installation:

• Measure the total vertical height of the fireplace

installation from the base of the fi replace assembly to
the approximate location of the bottom of the termination
cap.

• Subtract the effective height of the fi replace assembly

(see Figure 8.2) from the total vertical height to determine
the overall height of the chimney installation.

• Create a schematic for your application similar to Figure

8.2 showing components required (referring to Table
8.1). Figure 8.1 identifi es those components and where
used.

• Install a ceiling fi restop whenever the chimney penetrates

a fl oor/ceiling.

NOTICE:

A maximum of two pairs of offsets and returns

may be used.

CAUTION! Risk of Fire and/or Asphyxiation! DO

NOT connect this fi replace to a chimney fl ue servicing
another appliance. DO NOT connect to any air distribu-
tion duct or system. These actions could cause over-
heating/fi re in the chimney fl ue, or release of exhaust
fumes into the living areas.

Heatilator • A36C & A42C • 28396 • Rev AG • 11/08

HEIGHT OF CHIMNEY COMPONENTS

in.

mm

Chimney Stabilizer

SL3

4-3/4

121

Ceiling Firestops

FS338

0

0

FS339

0

0

FS340

0

0

Offsets/Returns

SL315

13-3/8

340

SL330

15-1/2

394

Roof Flashing

RF370

0

0

RF371

0

0

Chimney Sections*

SL306

4-3/4

121

SL312

10-3/4

273

SL318

16-3/4

425

SL324

22-3/4 578

SL336

34-3/4 883

SL348

46-3/4 1187

* Dimensions refl ect effective height.

This manual is related to the following products: