Rigging

Rigging holes are provided on all models. Caution should be

exercised when moving these units. To prevent damage to

the unit housing during rigging, cables or chains used must

be held apart by spacer bars. The mounting platform or base

should be level and located so as to permit free access of

supply air. The unit weather hood may be removed for the

rigging process. The condensing unit cover (wrapper) should

be left in place.

Access Requirements

Provide adequate space at the compressor end of the unit for

servicing. Provide two (2) feet of space above unit for service.

Mounting

The system requires an opening in the ceiling to the

dimensions stated on page 3. Mounting rails are located

at both ends of the chassis. Mounting rails may be used to

attach unit to ceiling. Through-bolts should be insulated or

non-conductive to prevent sweating. The chassis is weather

stripped around the air grille and will seal to the box roof.

The trim ring (shipped loose), when provided, should be

installed around the air diffuser when secured with the

hardware provided. Be sure to adhere to your local standard

construction codes.

Inspection

1. Each shipment should be carefully checked against the

bill of lading.

2. The shipping receipt should not be signed until all items

listed on the bill of lading have been accounted for.

3. Check packaging for signs of damage.
4. Any shortage or damages should be immediately

reported to the delivering carrier.

5. Damaged material becomes the delivering carrier’s

responsibility, and should not be returned to the

manufacturer unless prior approval is given to do so.

6. When unpacking the system, care should be taken to

prevent damage.

7. Avoid removing the shipping base until the unit has been

moved to the final destination.

8. Complete warranty return card for each unit and mail to

Heatcraft Refrigeration Products.

General Safety Information

1. Installation and maintenance to be performed only by

licensed contractor.

2. Ensure that the structural integrity of the box can

withstand the weight of the

(See page 2 for unit

weights).

3. Avoid contact with sharp edges and coil surfaces.

They are a potential injury hazard. Wear gloves during

moving and rigging.

4. Make sure all power sources are disconnected before

any service work is done on units.

Trim Pieces (4)
Overlap as Shown

Evaporator Grill

Self Drilling Screw

Ceiling of Walk-in.

Trim Ring

Installation

Detail

TABLE 4

Control Factory Default Settings

PTT

Models

Temperature

Set Points

Defrost

Start Times

Defrost Duration

(Maximum)

Drip

Time

Fan

Delay

Defrost Termination

Set Point

EZY

Default

H - Cooler Models

Air Defrost

38˚F

4 / day

60 min.

38˚F

3

M - Cooler Models

Electric Defrost

34˚F

4 / day

40 min.

2 min.

2 min.

65˚F

2

L - Freezer Models

Electric Defrost

-10˚F

4 / day

40 min.

2 min.

2 min.

65˚F

1

Changing the EZY

1. Press Set button and hold in until the display flashes "PS".
2. Press the Set Button and the display will change to "0" and

will begin to flash.

3. Press the up button until "22" is displayed.
4. Press the Set button.
5. Press the down button 2 times. "EZY" will be displayed.
6. Press the Set button.
7. Select the proper number for the model needed by

pressing the up or down key.

• 1 - L Low temperature model
• 2 - M Med temperature model
• 3 - H High temperature model

8. Press Set and wait for unit to return out of programming

mode.

9. Disconnect power
10. Press the Set Button while turning unit On
11. "CE" should display to verify programming display