PRO

3

Top Mount Packaged Refrigeration System | Outdoor

Set 1 - Low Temperature Models - L6 w/ -10° F Set Point

Set 3 - High Temperature Models - H6 w/ 38° F Set Point

Set 2 - Medium Temperature Models - M6 w/ 34° F Set Point

Parameter

Description

Min

Max

Default

St

Set point

-30

30

-10

r1

Minimum set point value

-50

303

-30

r2

Maximum set point value

-30

150

30

c2

Minimum compressor off time

0

100

4

do

Type of Defrost

0

4

0

dI

Interval between defrost

0

199

6

dt

End defrost temperature set point

-50

127

65

dP

Maximum defrost duration ALARM_ED

1

199

60

d4

Defrost on power-up

0

1

1

dd

Dripping time

0

15

2

F0

Enable evaporator fan control

0

1

0

F2

Stop evaporator fan if compressor off

0

1

0

F3

Evaporator fan status during defrost

0

1

1

Fd

Post-dripping time

0

15

2

Set o Set 1 Set 2 Set 3 Set 4

Parameter

Description

Min

Max

Default

St

Set point

0

50

34

r1

Minimum set point value

-50

50

0

r2

Maximum set point value

0

150

50

c2

Minimum compressor off time

0

100

4

do

Type of Defrost

0

4

0

dI

Interval between defrost

0

199

6

dt

End defrost temperature set point

-50

127

65

dP

Maximum defrost duration ALARM_ED

1

199

60

d4

Defrost on power-up

0

1

1

dd

Dripping time

0

15

2

F0

Enable evaporator fan control

0

1

0

F2

Stop evaporator fan if compressor off

0

1

0

F3

Evaporator fan status during defrost

0

1

1

Fd

Post-dripping time

0

15

0

Set o Set 1 Set 2 Set 3 Set 4

Parameter

Description

Min

Max

Default

St

Set point

0

50

38

r1

Minimum set point value

-50

50

0

r2

Maximum set point value

0

150

50

c2

Minimum compressor off time

0

100

4

do

Type of Defrost

0

4

2

dI

Interval between defrost

0

199

6

dt

End defrost temperature set point

-50

127

40

dP

Maximum defrost duration ALARM_ED

1

199

40

d4

Defrost on power-up

0

1

0

dd

Dripping time

0

15

0

F0

Enable evaporator fan control

0

1

0

F2

Stop evaporator fan if compressor off

0

1

0

F3

Evaporator fan status during defrost

0

1

0

Fd

Post-dripping time

0

15

0

Set o Set 1 Set 2 Set 3 Set 4

Device Setup

3.

C

on

tr

ollers