Page 15: C on tr ollers

background image

15

PRO

3

Top Mount Packaged Refrigeration System | Outdoor

Alarm

Code Buzzer and Alarm Relay

LED

Alarm Description

Reset

Enable Alarm

parameters involved

E0

active

ON

probe 1 error= control

automatic

E1

not active

ON

probe 2 error= defrost

automatic

d0= 0 / 1 / 4, F0= 1

E2

not active

ON

probe 3 error= condenser/ product

automatic

[A4=10]

IA

active

ON

external alarm

automatic

[A4 = 1] [+A7]

dOr

active

ON

open door alarm

automatic

[A4 = 7/8][+A7]

LO

active

ON

low temperature alarm

automatic

[AL] [Ad]

HI

active

ON

high temperature alarm

automatic

[AH] [Ad]

EE

not active

ON

unit parameter error

not possible

EF

not active

ON

operating parameter error

manual

Ed

not active

ON

defrost ended by timeout

on first defrost ended

correctly

[dP] [dt] [d4] [A8]

dF

not active

OFF

defrost running

automatic

[d6=0]

cht

not active

ON

dirty condenser pre-alarm

automatic

[A4=10]

CHt

active

ON

dirty condenser alarm

manual

[A4=10]

EtC

not active

ON

clock alarm

by setting the time

if bands active

3.

C

on

tr

ollers

Rapid Parameter Set Selction (EZY)

The easy controller features the EZY parameter which is used to
quickly choose a list of parameters, with corresponding values, for
the control of the refrigeration system.

Table of Alarms and Signals

When an alarm is activiated, the display shows the corresponding
message that flashes alternating with the temperature; if fitter and
enabled, the buzzer and the alarm relay are also activiated.

All the alarms have automatic reset (that is, they stop when the
causes are no longer present), except for alarm 'CHt' which has
manual reset (instrument on/off using the UP button or by discon-
necting the power supply).

NOTE:

• to restore the slected rapid parameter set at any time, turn the

controller off and on again, while holding SET. The desplay shows
"CE" to indicate that the selected rapid set (EZY= 1, 2, 3) has again
over written the operating parameters, thus restoring the original
set of paremters;

• to restore all the parameters and return to the original default

values (factory settings), turn the controller off and on again
while holding DOWN and SET, until the display shows "CF". Use
this procedure with extreme car, as it may compromise the
fundamental control settings;

• EZY= 0 brings no change

Pressing the SET button mutes the buzzer, while the code displayed
and the alarm relay only go off when the causes of the alarm have
been resolved. The alarm codes are shown in the able below: