PRO

3

Top Mount Packaged Refrigeration System | Outdoor

Modifying the Parameters

PARAMETER NAVIGATION
The operating parameters, modifiable using the keypad, are divided
into two types: frequent (type F) and configuration (type C). Access
to the latter is protected by password (default= 22) to prevent
accidental or unauthorized modifications.
Accessing the type F parameters:

• press the SET button for more than 3 s (if there are active alarms,

mute the buzzer), the display shows the parameter code ‘PS’
(password);

• use the UP and DOWN buttons to scroll the parameters. The LED

corresponding to the category of parameters will be on;

• press SET to display the value associated with the parameter

increase or decrease the value using the UP or DOWN button
respectively;

• press SET to temporarily save the new value and display the

parameter again;

• repeat the procedure for any other parameters that need to be

modified;

• press the SET button for more than 3 s to permanently save the

parameters and exit the parameter setting procedure.

Accessing the type C parameters:

• press the SET button for more than 3 s (if there are active alarms,

mute the buzzer), the display shows the parameter code “PS”
(password);

• press the SET button to access the password setting;
• use the UP and DOWN buttons to scroll the numbers until

displaying “22” (password to access the parameters);

• press the SET button to confirm the password;
• use the UP and DOWN buttons to scroll the parameters. The LED

corresponding to the category of parameters will be on (see
Table below);

• press SET to display the value associated with the parameter

increase or decrease the value using the UP or DOWN button
respectively;

• press SET to temporarily save the new value and display the

parameter again;

• repeat the procedure for any other parameters that need to be

modified;

• press the SET button for more than 3 s to permanently save the

parameters and exit the parameter setting procedure.

Warnings:
If no button is pressed for 60 s, all the changes made to

the parameters, temporarily saved in the RAM, will be

cancelled and the previous settings restored.
The dAY, hr, Min parameters are not restored, as these are

saved instantly when entered.
If power is disconnected from the instrument before

saving the settings (pressing the SET button for 3 s), all the

changes made to the parameters and temporarily saved

will be lost.

Setting the Default Parameters

Warnings:
Running this procedure overwrites any custom parameter
settings.

To reset the default parameters:

• disconnect power from the instrument;
• reconnect power while holding the SET and DOWN buttons;
• the display will show the message “CF”;
• after a few seconds the instrument starts operating with the

default configuration. Any different parameter settings will
need to be updated.