Low temperature alarm (e2) – Hoshizaki REFRIGERATED PREP TABLE WITH RAISED RAIL 73168 User Manual
Page 28
28
2. Low Temperature Alarm (E2)
If the cabinet or rail temperature drops below the setpoint temperature by 9°F (5°C) or
more for more than y hours, "E2" is displayed. The default value of y is "1" (1 hour). The
value of y can be changed under "F4" on the service menu. (0=No delay; 1=1 hour)
Note:
• The low temperature alarm timer starts once the cabinet temperature drops 9°F
(5°C) below the setpoint temperature.
• The low temperature alarm feature operates even during defrost.
Reset Options
The alarm will automatically reset once the area temperature reaches the upper setpoint
temperature differential.
Possible Causes (for further details see "III.B. Service Chart")
• Ambient temperature is low.
• Trouble with the cabinet thermistor (black).
• Liquid line valve open.
• Evaporator fans not operating.
E2 Alarm
Timer Reset
E2 Alarm Reset
Power On
E2 Alarm Temperature
9°F (5°C) below setpoint temp.
Lower Setpoint Temperature
Differential -3.6°F (2°C)
E2 Alarm
Timer over
1 hour
Temperature Display
E2
Blinking
E2 Alarm Timer
under 1 hour
Setpoint Temperature and
Upper Setpoint Differential 0°F (0°C)
E2 Alarm