25

Failure code

FAILURE CODE
(CHECK THE WIRED

REMOTE

CONTROLLER)

TROUBLE SHOOTING

(outdoor unit)

*
*

1. Please contact the installers or distributors when trouble happens to repair it.
2. Turn the power off and power on again, if the failure code recurs, please inform the franchiser.
3. Failrue codes maked with are resumable.

NOTE!

*

Faulty 4-way valve
switching on

Coil of 4-way valve is disconnected, or faulty
outdoor PCB

25

POSSIBLE REASONS

Faulty sensor Tc

Sensor disconnected, or broken, or short circuit

26

Faulty sensor Toci

Sensor disconnected, or broken, or short circuit

2A

Low voltage protection

VDC<194V, too low voltage from power source

High voltage protection

VDC>400V, too high voltage from power source

2C

2D

Abnormal communication
between main PCB and
SPDU(or ISPM)

Communication cables broken, or not be well
connected, or faulty main PCB, or faulty SPDU
(or ISPM)

2E

Compressor be locked

Faulty compressor or SPDU(or ISPM)

Compressor vibration too big

Faulty compressor

Compressor lose position

Faulty SPDU(or ISPM)

Faulty compressor start

Faulty compressor or SPDU(or ISPM)

Faulty position checking
circuit

Faulty SPDU(or ISPM)

Compressor broken

Faulty compressor or SPDU(or ISPM)

32

33

34
35

37

38