24

Failure code

Abnormal communication

between wired controller and

indoor unit PCB

Drainage system abnormal

The short-connector disconnected, or at wrong
position, or the float switch broken down or the
float switch disconnected,or at wrong position

FAILURE CODE
(CHECK THE WIRED

REMOTE

CONTROLLER)

TROUBLE SHOOTING

(indoor unit)

TROUBLE SHOOTING

(ourdoor unit)

FAILURE CODE
(CHECK THE WIRED

REMOTE

CONTROLLER)

*

*

*

*

*

*

*

*

Abnormal communication
between chip TMP/807 and chip
TMP/846

0E

Faulty indoor unit PCB

POSSIBLE REASONS

Indoor unit address repeated

09

Wrong setting of indoor unit address

07

Wrong connection, or use the wired controller
be disconnected, faulty PCB

08

Faulty defrost sensor Te

Sensor disconnected, or broken, or short circuit

Faulty sensor Tao

Sensor disconnected, or broken, or short circuit

Faulty sensor Ts

Sensor disconnected, or broken, or short circuit

Faulty sensor Td

Sensor disconnected, or broken, or short circuit

Input overcurrent

Over current of the system, or broken of the
current sensor,or malfunction with indoor or
outdoor fan motors, or faulty PCB.

15

16

17

14

19

System high pressure
protection

High pressure switch is disconnected, or high
pressure switch worked, or Tc too high and
faulty outdoor fan motor when cooling, or
faulty indoor fan motors when heating, or
refrigerant overabundance

1E

System low pressure
protection

Low pressure switch is disconnected, or low
pressure switch worked, or Te too low and
faulty outdoor fan motors when heating, or
faulty indoor fan motor when cooling, or
refrigerant shortage

1F

IPM protection

IPM over current, or short circuit, or IPM
temperature too high, or IPM input voltage
too low,or faulty SPDU(or ISPM).

EEPROM fault

Faulty outdoor unit PCB

20

21

Over hot protection of
compressor

Serious lack of refrigerant of the system, or
the ambient temperature too high, or PMVs be
blocked

22

Over hot protection of SPDU
(or ISPM)

Ambient tempreatrue too high, or outdoor fan
be blocked, or bad air circulation of outdoor unit

23

DC fan motor fault

Fan is blocked, or the terminal is disconnected
from the PCB

24

POSSIBLE REASONS