Instructions to installation – haier AD122XLERA User Manual

Page 17

background image

Installation dimension:(mm)

Unit model

AD142XLERA
AD182XLERA

AD122XLERA

AD092XLERA

a

1002

538

b

483.5

483.5

c

131

131

d

1105

610

e

255

255

f

105

105

g

880

418

h

970

508

i

220

220

1.This series' indoor units are all low static pressure type(max. 20 Pa external static pressure
available ).
2.An access port must be provided during installation of indoor unit for maintenance.

15

When installing the ceiling concealed type indoor unit, a specially designed return air bellows
shall be installed, as shown in Figure 3, Figure 4.

Figure 3

Figure 4

A

Installing building roof

Ceiling

Air supply

Air outlet duct

Unit

Return air

Return air bellows

Air outlet grille

Air supply

No obstacles
within 1 m(0Pa)

Unit

Return air

Return air bellows

0.5m(0Pa)or 5m(50Pa)

Each air return and supply duct should fix to the floor precast slab by using an iron stand. Use
glue to seal the interface closely. Recommend the distance between the air return duct and the
wall is more than 150mm.

Instructions to installation

NOTE!

a

b

c

d

e

f

g

h

i