Shrouds – Heat & Glo Fireplace RUTHERFORD 50 User Manual

Page 32

background image

32

Allow a 1 in. (25 mm) air gap between
storm collar and chase top flashing

1/2 in. (13 mm) air space
established by spacers

1/2 in.
overhang

14 in. (345 mm)
diameter chimney
must extend at least
6 in. (152 mm) above
chase top flashing.

DuraChimney II
Pipe

1/2 in.
(13 mm)

Field-fabricated

spacers for chase

top flashing

Chase Top

Flashing or
Chase Pan

Storm Collar

20 in. diameter

opening

Chimney Cap

Maintain 2 in. (51 mm)

clearance between

DuraChimney II and

chase enclosure

• Chase top shrouds may be field constructed where

permitted by regional building codes.

WARNING! Risk of Fire! Shrouds must be constructed as
specifi ed. Improper construction may overheat chase top.

NOTICE:

Some regional codes require an agency-Listed

shroud. Consult your local building offi cials.

10

10

Shrouds

• Hearth & Home Technologies Inc. supplies UL listed

shrouds. See your dealer for details.

A. Shroud Requirements

Figure 10.1 Shroud Requirements

Shrouds can either be fi eld-fabricated or factory-fabricated,
but they must meet the requirements as specifi ed in these
instructions. Shrouds must be constructed of a minimum
24 ga (.024 in.) stainless steel, aluminized steel, galva-
nized steel, or copper. Other materials may also be used,
such as brick, mortar, stucco, stone, etc. provided they are
completely non-combustible. Check with your local building
code authroities for any additional shroud requirements.
Shrouds must be able to be removed to allow chimney ac-
cess to properly clean the chimney. DuraChimney II instal-
lations which include the use of a shroud must comply with
the following requirements (Figure 10.1)

• DuraChimney II must maintain at least 2 in. (51 mm)

clearance from combustible materials.

• The chase enclosure must be ventilated.
• The chase top fl ashing or fi eld-fabricated chase pan must

be used. Field-fabricated chase pans are acceptable if
they meet these requirements:
- Material must be 24 ga (.024 in) galvanized steel or

equivalent.

- Chase pan must have opening 3 in. (76 mm) larger

than outside diameter of chimney pipe with at least a
1/2 in. (13 mm) upturned fl ange/collar.

- Chase pan must overhang chase by 1/2 in. (13 mm)

per side for proper air fl ow.

- Chase pan must have a 1 in. (25 mm) down turned

outside edge (weather prtection).

Heat & Glo • RUTHERFORD-50 • 4059-333 Rev D • 07/08