Framing & clearances, A. select fireplace location – Heat & Glo Fireplace RUTHERFORD 50 User Manual

Page 17

background image

17

6

6

Framing & Clearances

A

F

D

B

C

5/8 in. (16 mm) all
configurations

1-1/2 in. min. air space
from fireplace to
combustible materials.
1/2 in. min. air space at
nailing flanges.

Note:

In an exterior chase
or projecting into a
garage

Across a
corner

As a
room
divider

Along a wall

92 in.

(2337 mm)

G

B

E

Note: In addition to these

framing dimensions, also
reference the following
sections:
• Clearances (6.B.)
• Framing (6.D.)
• Mantel Projections

(6.C)

• Fireplace Dimensions

(14.A.)

48 in.

(1219 mm)

MINIMUM

24 in. (610 mm)

from fireplace opening to

any perpendicular wall

A

B

G

G

B

))))))

))

)))

)

)))

))))

))

)))

))))

)))

)))))))))))))))

))))

)))

)))))))))))))))

))))

))))

)))

))

)))

))

))

))

)))

))))

)))

))

)))

)))

))

Figure 6.1 Fireplace Locations

A. Select Fireplace Location

NOTICE: Both outside air kits MUST be installed.

Model #

A

B

C

D

E

F

G

RUTHERFORD-50

in.

85 7/8

61 7/8

103 1/4

51 5/8

25 1/4

73

29 3/8

mm

2181

1572

2623

1311

641

1854

746

Heat & Glo • RUTHERFORD-50 • 4059-333 Rev D • 07/08