B − 22 – Hitachi X200 Series User Manual

Page 249

background image

The following table lists holding registers for the “D” Group Monitor Functions.

List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

D001 Output frequency

monitor

R

Real-time display of output
frequency to motor, from 0.0 to

400.0 Hz

1002h

0 to 4000

0.1 Hz

D002 Output current

monitor *1

R

Filtered display of output

current to motor (100 ms
internal filter time constant),

range is 0 to 200% of inverter

rated current

1003h

0 to 2000

0.1%

D003 Rotation direction

monitor

R

Three different indications:

00...Stop
01...Forward

02...Reverse

1004h

0,1,2

D004

(high)

R

1005h

D004

(low)

Process Variable (PV),
PID feedback monitor

R

Displays the scaled PID process
variable (feedback) value (A075

is scale factor), range is 0.00 to

9999.00

1006h

0 to

999900

0.00%

times

const.

D005 Intelligent input

terminal status

R

Displays the state of the
intelligent input terminals [x],

Bit 0 = [1] to Bit 4 = [5]

1007h

0 to 63

D006 Intelligent output

terminal status

R

Displays the state of the

intelligent output terminals [x],

Bit 0 = [11], Bit 1 = (Don’t Care),
Bit 2 = [AL]

1008h

0 to 7

D007

(high)

R

1009h

D007

(low)

Scaled output

frequency monitor

R

Displays the output frequency

scaled by the constant in B086.
Decimal point indicates range:

0.00 to 39960.00

100Ah

0 to

3996000

0.01 Hz

times

const.

D013 Output voltage

monitor

R

Voltage of output to motor, range

is 0.00 to 200.00%

100Ch

0 to

20000

0.01%

D016

(high)

R

100Eh

D016

(low)

Cumulative operation

RUN time monitor

R

Displays total time the inverter

has been in RUN mode in hours.
Range is 0 to 999999

100Fh

0 to

999999

1 hour

D017

(high)

R

1010h

D017

(low)

Cumulative power-on

time monitor

R

Displays total time the inverter

has been in RUN mode in hours.

Range is 0 to 999999

1011h

0 to

999999

1 hour

D018 Fin temperature

monitor

R

Display the Fin temperature in
0.0~200.0

°C

116Ah 0 to 2000

0.1

°C

D080 Trip counter

R

Number of trip events, range is 0

to 65535

0011h 0 to 65535 1 trip

event

D102 DC voltage monitor

R

Voltage of DC bus inside

inverter,Range is 0.0 to 999.9

116Ch 0 to 9999

0.1 V

D104 Electronic thermal

monitor

R

Accumulated value of electronic

thermal detection, range is from
0.0 to 100.0

116Dh 0 to 1000

0.1 %

Note 1:

Assume that the inverter current rating is 1000 (for D002).

B22

Appe

ndix B