1. Total KW Needed

Approximate KW =

2. Number Of Steps Recommended

Rule of thumb for calculating the recommended number of
steps required. Use Step A or B below, whichever is higher.

A. Number of Steps =

(Based on approx. 10°F. temp. rise per step)

B. Number of Steps =

CFM x TD (F)

3000

300 x Total Heater KW

CFM

Total Heater KW

Maximum KW per step

E

lectric heaters are UL listed for duct installation. The UL

label applies to the heater only, not the complete air handler.

Heaters are furnished as a separate section and are available
with insulated or uninsulated casings. Controls such as
contactors, fuses, etc., may be factory installed and wired in
the heater section end panel provided the number of control
steps is not excessive.

Remote control panels are also available.