beautypg.com

Coil performance- direct expansion mbh/sq ft, Actual capacity will vary with coil circuiting – Heatcraft Refrigeration Products HCS User Manual

Page 21

background image

21

ENT AIR

Table 18:

Capacity Correction Factors* To Coil Performance

Of 67°F Wb And 40°F Evaporating

Ent Air WB

Refrigerant Evaporating Temperature °F.

Temp. °F.

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

60

0.820 0.794 0.768 0.740 0.713 0.685 0.656 0.628 0.598 0.568 0.538 0.506 0.475 0.442 0.409 0.376

61

0.862 0.837 0.810 0.783 0.756 0.727 0.698 0.670 0.640 0.610 0.580 0.548 0.517 0.484 0.452 0.418

62

0.907 0.881 0.854 0.827 0.799 0.771 0.743 0.714 0.684 0.654 0.623 0.592 0.561 0.528 0.496 0.462

63

0.950 0.923 0.897 0.870 0.842 0.814 0.785 0.756 0.727 0.696 0.666 0.635 0.603 0.571 0.538 0.505

64

0.994 0.969 0.942 0.914 0.887 0.859 0.831 0.802 0.772 0.742 0.712 0.680 0.649 0.616 0.583 0.550

65

1.040 1.014 0.988 0.960 0.933 0.905 0.876 0.847 0.818 0.788 0.757 0.726 0.694 0.662 0.629 0.596

66

1.087 1.061 1.035 1.008 0.980 0.952 0.923 0.894 0.864 0.835 0.804 0.773 0.741 0.709 0.676 0.642

67

1.136 1.109 1.083 1.055 1.028 1.000 0.971 0.943 0.913 0.883 0.852 0.822 0.789 0.757 0.724 0.691

68

1.185 1.158 1.132 1.105 1.077 1.050 1.020 0.992 0.962 0.932 0.901 0.870 0.838 0.806 0.773 0.740

69

1.235 1.209 1.182 1.155 1.127 1.100 1.071 1.042 1.012 0.982 0.952 0.920 0.889 0.856 0.824 0.790

70

1.286 1.260 1.235 1.206 1.179 1.152 1.122 1.094 1.063 1.033 1.003 0.972 0.940 0.908 0.875 0.841

71

1.339 1.313 1.285 1.260 1.231 1.203 1.175 1.146 1.115 1.086 1.055 1.024 0.993 0.960 0.927 0.894

72

1.393 1.365 1.340 1.314 1.285 1.257 1.229 1.200 1.170 1.140 1.110 1.079 1.046 1.015 0.981 0.948

73

1.450 1.422 1.395 1.369 1.340 1.313 1.285 1.255 1.225 1.195 1.165 1.134 1.103 1.070 1.036 1.003

74

1.505 1.479 1.451 1.425 1.396 1.370 1.340 1.310 1.281 1.252 1.221 1.190 1.159 1.126 1.094 1.060

* Note: correction factor = (enthalpy of air temperature - enthalpy of evaporator temperature) in BTU/LB divided by 16.39

Coil Performance- Direct Expansion MBH/SQ FT

Table 17
Wet Evaporator
Capacity

1/2" and 5/8" tube, entering air 80°F. DB, 67°F. WB

Type A and Type 5, direct expansion at 40ºF. evaporating, cooling capacities

MBH per SQ FT of coil face area

FPM, Type A Coils (1/2" DIA.)

FPM, Type 5 Coils (5/8" DIA.)

Rows

FPI

400

450

500

550

600

400

450

500

550

600

6

11.3

12.1

12.8

13.4

14.0

13.1

13.8

14.5

15.2

15.8

8

13.0

13.9

14.7

15.4

16.1

14.9

15.8

16.6

17.4

18.1

3

10

14.4

15.3

16.2

17.0

17.8

16.2

17.2

18.2

19.0

19.8

12

15.4

16.5

17.4

18.3

19.1

17.3

18.4

19.4

20.3

21.2

14

16.3

17.4

18.4

19.3

20.2

18.0

19.2

20.4

21.4

22.4

6

14.0

15.0

16.0

16.9

17.7

15.8

16.8

17.8

18.7

19.5

8

15.9

17.1

18.2

19.2

20.1

17.7

18.9

20.0

21.0

22.0

4

10

17.4

18.7

19.8

20.9

22.0

19.0

20.4

21.7

22.8

23.9

12

18.5

19.9

21.2

22.3

23.4

19.9

21.4

22.8

24.1

25.3

14

19.4

20.9

22.2

23.5

24.6

20.7

22.3

23.8

25.2

26.5

6

15.9

17.1

18.3

19.3

20.3

17.9

19.2

20.5

21.6

22.6

8

18.3

19.7

21.1

22.3

23.5

19.8

21.3

22.7

24.0

25.2

5

10

19.8

21.3

22.8

24.2

25.5

21.0

22.7

24.3

25.7

27.1

12

20.9

22.6

24.2

25.6

27.0

21.8

23.6

25.4

27.0

28.5

14

21.8

23.6

25.3

26.8

28.3

22.5

24.4

26.3

28.0

29.6

6

17.8

19.2

20.5

21.7

22.8

19.7

21.2

22.7

24.0

25.3

8

19.7

21.3

22.7

24.1

25.4

21.4

23.1

24.8

26.3

27.8

6

10

21.1

22.8

24.4

25.9

27.2

22.5

24.4

26.3

28.0

29.7

12

22.1

23.9

25.6

27.2

28.7

23.3

25.3

27.3

29.2

31.0

14

22.9

24.8

26.6

28.2

29.8

23.9

26.0

28.1

30.1

32.0

6

20.9

22.7

24.3

25.9

27.4

22.3

24.2

26.0

27.7

29.4

8

22.7

24.7

26.6

28.4

30.0

23.8

25.9

28.0

29.9

31.7

8

10

23.9

26.1

28.1

30.1

31.9

24.6

27.0

29.3

31.3

33.3

12

24.8

27.1

29.3

31.3

33.2

25.2

27.7

30.1

32.4

34.6

14

25.4

27.8

30.1

32.2

34.2

25.7

28.2

30.7

33.1

35.4

Actual capacity will vary

with coil circuiting

Note: Please contact your representative for ARI ratings for coils. These tables are only estimates.

For extimates for other web bulb and evaporator temperatures, multiply by correction

factors in Table 18.