beautypg.com

Air pressure drops- cabinets, filters, wet coils – Heatcraft Refrigeration Products HCS User Manual

Page 41

background image

41

Air Pressure Drops- Cabinets, Filters, Wet Coils

Cabinet And Filter Air Pressure Drop

Air Pressure Drop - inches of water

Air Velocity^ - Feet per minute

Component

200

250

300

350

400

450

500

550

600

Cabinet:

V Style Cabinet^^

.10

.13

.16

.20

.24

.29

Economizer Section^^

.02

.03

.03

.04

.05

.06

.07

Filters:

Throwaway

2" Depth

.05

.08

.11

.15

.19

.24

.28

—— ——

flat & hi

35% Efficient , Pleated

2" Depth

.08

.10

.13

.16

.21

.25

.30

.37

——

capacity

Permanent, Aluminum, Cleanable

2" Depth

.03

.04

.06

.08

.10

.13

.15

.18

.21

flat, 4"

35% Efficient , Pleated

4" Depth

.06

.07

.10

.13

.17

.20

.25

.29

.34

(60 - 65%) Efficient

21" Depth

.12

.16

.21

.26

.32

.38

.45

Filters:

Bag Filter

30" Depth

.19

.24

.28

.33

.37

.41

.44

37" Depth

.12

.17

.23

.27

.33

.37

.41

Medium

(80 - 85%) Efficient

21" Depth

.14

.20

.26

.32

.38

.44

.51

Bag Filter

30" Depth

.23

.28

.34

.40

.47

.51

.55

37" Depth

.15

.21

.26

.32

.38

.45

.52

and

(90 - 95%) Efficient

21" Depth

.20

.28

.36

.44

.52

.61

.70

Bag Filter

30" Depth

.32

.39

.46

.53

.60

.66

.72

37" Depth

.22

.29

.36

.44

.54

.60

.68

High

(60 - 65%) Cartridge Filter

6" Depth

.15

.20

.26

.33

12" Depth

.22

.28

.34

.41

.50

.58

.68

(80 - 85%) Cartridge Filter

6" Depth

.22

.29

.37

.46

Efficiency

12" Depth

.26

.32

.38

.46

.55

.64

.74

(90 - 95%) Cartridge Filter

6" Depth

.25

.34

.44

.56

12" Depth

.29

.35

.42

.50

.59

.70

.82

The filter air pressure drop is for air through clean filters.

Type A (1/2" O.D.) Wet Coil Air Pressure Drop* Type 5 (5/8" O.D.) Wet Coil Air Pressure Drop*

Rows

Fin

Air Velocity - Feet per minute^

Rows

Fin

Air Velocity - Feet per minute^

Series 400

450

500

550

600

650

Series

400

450

500

550 600

650

6

0.18 0.22 0.26 0.30 0.34

0.39

6

0.25

0.30

0.36

0.42 0.49 0.56

8

0.22 0.27 0.32 0.37 0.42

0.48

8

0.31

0.37

0.44

0.52 0.60 0.68

3

10

0.26 0.32 0.37 0.43 0.50

0.56

3

10

0.36

0.44

0.52

0.58 0.67 0.79

12

0.30 0.37 0.43 0.50 0.57

0.65

12

0.42

0.50

0.59

0.66 0.76 0.87

14

0.34 0.41 0.49 0.56 0.64

0.73

14

0.45

0.54

0.64

0.74 0.85 0.97

6

0.24 0.29 0.35 0.40 0.47

0.53

6

0.33

0.40

0.48

0.56 0.65 0.74

8

0.30 0.36 0.43 0.50 0.57

0.65

8

0.41

0.50

0.59

0.69 0.80 0.91

4

10

0.35 0.43 0.51 0.59 0.67

0.77

4

10

0.48

0.58

0.69

0.81 0.93 1.06

12

0.41 0.49 0.58 0.68 0.77

0.88

12

0.56

0.67

0.79

0.92 1.02 1.20

14

0.46 0.56 0.66 0.76 0.87

0.99

14

0.63

0.75

0.89

1.03 1.14 1.34

6

0.31 0.38 0.45 0.53 0.61

0.70

6

0.41

0.50

0.60

0.70 0.81 0.93

8

0.39 0.47 0.56 0.65 0.74

0.84

8

0.51

0.62

0.74

0.86 0.99 1.13

5

10

0.46 0.55 0.65 0.75 0.86

0.97

5

10

0.60

0.73

0.87

1.01 1.12 1.32

12

0.53 0.63 0.74 0.85 0.97

1.10

12

0.69

0.84

0.99

1.11 1.27 1.50

14

0.59 0.71 0.83 0.95 1.09

1.22

14

0.78

0.94

1.11

1.24 1.42 1.68

6

0.37 0.46 0.54 0.64 0.74

0.84

6

0.49

0.60

0.72

.84 0.98 1.12

8

0.46 0.56 0.67 0.78 0.90

1.03

8

0.61

0.74

0.88

1.03 1.19 1.36

6

10

0.55 0.67 0.79 0.92 1.05

1.18

6

10

0.72

0.88

1.04

1.21 1.40 1.59

12

0.63 0.77 0.90 1.04 1.19

1.34

12

0.83

1.01

1.19

1.38 1.59 1.80

14

0.72 0.86 1.01 1.17 1.33

1.49

14

0.94

1.13

1.33

1.55 1.77 2.01

6

0.51 0.62 0.74 0.87 0.99

1.12

6

0.66

0.80

0.96

1.12 1.30 1.49

8

0.63 0.77 0.90 1.05 1.20

1.35

8

0.82

0.99

1.18

1.38 1.59 1.82

8

10

0.75 0.90 1.06 1.23 1.40

1.58

8

10

0.97

1.17

1.39

1.62 1.86 2.12

12

0.86 1.03 1.21 1.40 1.59

1.79

12

1.11

1.34

1.58

1.84 2.12 2.41

14

0.96 1.15 1.35 1.56 1.78

2.01

14

1.25

1.51

1.78

2.06 2.36 2.68

* Wet coil air pressure drop for air entering at 80 °F DB and 67 °F WB over rippled high efficiency fins. Inches of water.
^ Air velocity = CFM divided by coil or filter face area in square feet. See table at top of page 40.
^^ Use face area of large coil to calculate air speed through AHV cabinet and economizer section.