Motor control acce ssor ie s – Hitachi SJ100 User Manual
Page 167

SJ100 Inverter
Motor Control
Acce
ssor
ie
s
5–9
The table below lists 400V-class inverter models
with built-in braking units. Depending on the
desired braking torque or on the inverter model,
the resistor selection specifies multiple resistors
in a parallel or series combination. The example
diagram shows a parallel configuration. Please
refer to the braking resistor documentation for
detailed wiring diagrams.
Selecting Braking Resistors for External Braking Units
200V Class Inverters – The following tables
specify the braking options for 200V class
SJ100 inverters and the braking torque for
each option. You can connect a single braking
unit to the inverter, or two braking units for
additional stopping torque.
Inverter
JRB x (2) parallel
+
RB
400V Class
Dynamic Braking Resistor Selection
JRB Series
SRB/NSRB Series
HRB Series
SJ100
Model
Number
HP
Type &
(Qty)
Total
Ohms
Total
Watts
Max.
Duty
Cycle
(%)
Type &
(Qty)
Total
Ohms
Total
Watts
Max.
Duty
Cycle
(%)
Type &
(Qty)
Total
Ohms
Total
Watts
Max.
Duty
Cycle
(%)
004HFE/HFU
1/2
120–1
180
120
2.0
200–1
180
200
4.0
007HFE/HFU
1
120–1
180
120
2.0
200–1
180
200
4.0
015HFE/HFU
2
120–1
180
120
2.0
200–1
180
200
4.0
022HFE/HFU
3
120–2
100
120
1.5
200–2
100
200
3.0
030HFE
4
120–2
100
120
1.5
200–2
100
200
3.0
040HFE/HFU
5
120–2
100
120
1.5
200–2
100
200
3.0
055HFE/HFU
7.5
120–4
x (2) in
series
70
240
1.0
400–1
x (2) in
series
70
800
7.5
RB2
x (2) in
series
70
1200
10.0
075HFE/HFU
10
70
240
1.0
70
800
7.5
70
1200
10.0
Inverter
+
–
Braking
unit
Braking
unit