Step 3. installing the vent system – Heat & Glo Fireplace LCOR-HV-IPI User Manual

Page 23

background image

Heat & Glo • PIER-HV-IPI, ST-HV-IPI, L&R-COR-HV-IPI • 2005-900 Rev. M • 9/08

23

Figure 7.

Vent System Components and Termination Kits

Step 3. Installing the Vent System

A. Vent System Approvals

These models are approved to use DVP series direct vent
pipe components and terminations (see Figures 6 and 7).
Approved vent system components are labeled for identifi-
cation. This pipe is tested and listed as an approved com-
ponent of the fireplace. The pipe is tested to be run inside
an enclosed wall. There is no requirement for inspection
openings at each joint within the wall. There is no required
pitch for horizontal vent runs. NO OTHER VENTING SYS-
TEMS OR COMPONENTS MAY BE USED
.

Detailed installation instructions are included with each vent
termination kit and should be used in conjunction with this
Installers Guide.

The flame and ember appearance may vary based on the
type of fuel burned and the venting configuration used.

Identifying Vent Components

The vent systems installed on this gas fireplace may in-
clude one, two, or three 90°

elbow assemblies. The rela-

tionships of vertical rise to horizontal run in vent configura-
tions using 90° elbows MUST BE strictly adhered to. The
rise to run relationships are shown in the venting drawings
and tables. Refer to the diagrams on the next several pages.

NOTE: Two 45° elbows may be used in place of one
90° elbow. Rise to run ratios in the vent system must
be followed if 45° elbows are used.

This model has a 45

0

elbow built into it. It may be posi-

tioned to vent either horizontal or vertical. Depending on the
installation, decide which direction the elbow should be fac-
ing. Remove the 8 screws from the corner cover plate. Po-
sition the 45

0

elbow as desired and replace the corner cov-

er plate with the 8 screws.

HORIZONTAL
TERMINATION

WALL FIRESTOP

90 DEGREE
ELBOW

PIPE LENGTH

CEILING
FIRESTOP

VERTICAL
TERMINATION

STORM COLLAR

ROOF FLASHING

Terminations Kits

(Required to have a minimum of 3
feet of vertical in the vent system)

DVP-TV

PVK-80

DVP-TVHW

DVP-TRAP

DVP-TB1