Remote intelligent power supply, Power supply, Features – Honeywell INTELLIGUARD 9000 User Manual
Page 3
INTELLIGUARD 9000™ SECURITY SYSTEM
3
74-3035—2
Wiring Connections: Table 1 describes the connections
between the I9000 CU and its input and output devices. Use a
RS-232 cable to connect the CU to the EBI. Use twisted pair
cable to connect the RS-485 CU ports to the I9000 input and
output devices.
NOTE: All devices should be equally divided among the two
RS-485 communication lines to maximize system
performance. See Control Center 2 Keypads and
Area Keypads sections for details.
Enclosure: 0.06 in. (1.52 mm) cold rolled steel.
Dimensions: 14-7/16 in. (367 mm) wide x 10-5/16 in. (262
mm) high x 3-1/8 in. (79 mm) deep.
Weight: 8.66 lb (3.93 kg), without batteries.
Approvals: UL, ULC, CE.
Table 1. I9000 CU Cable, Baud Rate Connections to Input,
Output Devices.
NOTE: Device to CU wire gauge is 22 AWG. Voltage drops
due to load and cable length may require an increase
in conductor size to ensure devices remain within
operational limits.
Power Supply
The I9000 and the RIPS operate from 16 Vac, 50/60 Hz (37 to
40 VA) provided by a locally supplied power transformer. For
ULI installations, this is a Silent Knight model 9220
Transformer with Silent Knight model 4165 Enclosure or listed
equivalent. For ULC installations (Canada only), this is a
5660-051 Honeywell Transformer Assembly.
Remote Intelligent Power Supply
A Remote Intelligent Power
Supply (RIPS) consists of an
I9000 enclosure containing the
8003-295 Intelligent Switching
Power Supply (ISP) without an
ICP II Control Board. The RIPS
is required when the installation
power requirements exceed the
available control unit power.
Each I9000 CU supports a maximum of seven RIPS. The
control unit supports up to eight ISPs (four per RS-485 port),
seven in the RIPS (one per RIPS) and one located in the
I9000 control unit enclosure. Depending on the installation
power backup requirements, up to two batteries can be
connected to each ISP. When the programmable outputs are
used, two batteries are recommended for those respective
RIPS.
Features
• Same as ISP features except the tamper input is factory
wired to the RIPS enclosure tamper switch.
• When cover is closed, the red LED Communication
Indicator is automatically disabled to save power.
Model: 8003-217 Remote Intelligent Power Supply (RIPS).
Transformer Electrical Ratings: Each RIPS must have its
own transformer connected to a non-switched electrical cir-
cuit.
Type: Class II Energy Limiting.
Output Voltage: 16 Vac.
Output Current: 2.3A.
Power Rating: 37 VA.
RIPS Electrical Ratings:
Operating Voltage: 13.6 Vac to 17.6 Vac.
ISP Power Consumption During AC Failure: 20 mA at
13.8 Vdc (maximum battery voltage). Add programmable
output load current to this value if the output is used.
Outputs: 2 x 400 mA maximum at 12.9 Vdc ± 4%. One pro-
grammable switched output at 1A, 12 Vdc.
NOTE: Power for the ISP programmable switched output is
partly obtained from the standby batteries. There-
fore, this output should be used to drive loads such
as sirens and bells for short durations (15 minutes
maximum). Otherwise the battery capacity will be
reduced and this will affect the total backup time
available for the devices connected to that ISP.
Standby Batteries:
Model: YUASA P/N NP7-12 or equivalent.
Electrical Ratings: 12V, 7 Ah.
Type: Sealed lead acid.
Quantity: Two maximum.
Dimensions: 2-9/6 in. (65 mm) wide x 3-7/8 in. (98 mm) high
(including terminals), x 6 in. (152 mm) deep.
Weight: 6.17 lb (2.65 kg).
Communication: RS-485 receiving and transmitting signals.
Enclosure: 0.06 in (1.52 mm) cold rolled steel.
Dimensions: 14-7/16 in. (367 mm) wide x 10-5/16 in.
(262 mm) high x 3-1/8 in. (79 mm) deep.
Weight: 8.62 lb (3.91 kg).
Approvals: UL, ULC, CE.
Designation
COM1, COM2
COM3
Application
I9000 CU and
peripherals
EBI Interface
Electrical Interface RS-485
RS-232
Cable
Twisted Pair (two or
three pairs)
Shielded Cable,
four conductors
Maximum Distance 3277 ft (999m)
75 ft (22m)
Baud Rate
4800 Baud
75-2400 Baud,
Programmable
Word Format
10 Bits (Start, 7
Data, Even Parity,
Stop)
12 Bits (1 Start, 8
Data, 1 Parity, 2
Stop)