Table C2. Configuration Variables for Excel 10 FCU Controllers

NV name

field name

engineering units:

English (metric) or states

plus range

digital

state

or

value

default comments

nciFcuConfig output_type[0]

BYTE
FLOATING
ONE_STAGE
TWO_STAGE
THREE_STAGE
PWM
THERMAL
FLOATING_MID


0
1
2
3
4
5
6

FLOATING

This configuration variable specifies the output type to drive the
connected actuator for the output 1:
FLOATING/FLOATING_MID - This setting considers valve_reverse[]
and cycle_time[]. Synchronization is performed at every restart and at
least once per day.
ONE_STAGE - Triac 2 is not used.
TWO_STAGE/THREE_STAGE - Triac 1 and 2 used (triac 1 and 2 both
ON for stage 3). When configured as multistage, cycle_time and
min_stage_off_time are considered.
PWM/THERMAL - Triac 2 is not used. Triac 1 operates as a pulse-
width modulated output, and the cycle time must be specified in
cycle_time[]. For PWM outputs, PwmZeroPosn and PwmFullPosn must
also be specified.

nciFcuConfig output_type[1]

BYTE
FLOATING
ONE_STAGE
TWO_STAGE
THREE_STAGE
PWM
THERMAL
FLOATING_MID


0
1
2
3
4
5
6

FLOATING

This configuration variable specifies the output type to drive the
connected actuator for the output 2 (see above).






nciFcuConfig valve_reverse_0 Bit

DIRECT
REVERSE


0
1

DIRECT

This configuration variable applies to only those outputs that have been
configured as FLOATING, PWM, or THERMAL and specifies the
direct/reverse operation of output 1.

nciFcuConfig valve_reverse_1 Bit

DIRECT
REVERSE


0
1

DIRECT

This configuration variable applies only to those outputs that have been
configured as FLOATING, PWM, or THERMAL and specifies the
direct/reverse operation of output 2.

nciFcuConfig fan_interlock_0 Bit

NO
YES


0
1

NO

This configuration variable configures an interlock between fan and
output 1 to provide equipment protection for electric heat or
compressor. fan_interlock_0=1 enables interlock, which guarantees
output1 to be driven only when the fan is running.

nciFcuConfig fan_interlock_1 Bit

NO
YES


0
1

NO

This configuration variable configures an interlock between fan and
output 2 to provide equipment protection for electric heat or
compressor. fan_interlock_1=1 enables interlock, which guarantees
output2 to be driven only when the fan is running.