EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

EN2B-0285GE51

R0909

29

Switching Levels

See section "Configurations" on page 12 for more information about parameters.

Table 20. FCU Controller switching levels configuration options

function

configuration options

default

cooling stage 1 switching level

0 to 100%

5%

heating stage 1 switching level

0 to 100%

5%

cooling stage 2 switching level

0 to 100%

50%

heating stage 2 switching level

0 to 100%

50%

cooling stage 3 switching level

0 to 100%

75%

heating stage 3 switching level

0 to 100%

75%

cooling hysteresis

0 to 100%,

10%

heating hysteresis

0 to 100%

10%

Notes:

1. Stage switching levels and hysteresis are used for fan control as well as multi-stage heating/cooling outputs

control.

Zone Options

The Zone configuration options are listed in the following table. See section "Configurations" on page 12 for more information

about parameters.

Table 21. FCU Controller zone configuration options

function

configuration options

default

cooling occupied setpoint

50 to 95°F (10 to 35°C)

73.4°F (23°C)

heating occupied setpoint

50 to 95°F (10 to 35°C)

69.8°F (21°C)

cooling standby setpoint

50 to 95°F (10 to 35°C)

77°F (25°C)

heating standby setpoint

50 to 95°F (10 to 35°C)

66.2°F (19°C)

cooling unoccupied setpoint

50 to 95°F (10 to 35°C)

82.4°F (28°C)

heating unoccupied setpoint

50 to 95°F (10 to 35°C)

60.8°F (16°C)

Notes:

1. Ensure that unoccupied heating

standby heating


Miscellaneous

The options available in the Miscellaneous tab are listed in the following table. See section "Configurations" on page 12 for more

information about parameters.

Table 22. FCU Controller miscellaneous configuration options

function

configuration options

default

Bypass time

0 to 1080 minutes

180 minutes

Override priority

last wins - the last command from either the wall module or from the

network has priority.
network wins - a network command always has priority until canceled.

last wins

Demand limit control bump

0 to 18 DDF (0 to 10 K)

3.6 DDF (2 K)

Cool rec ramp

(cooling optimum start gradient)

-36 DDF/hour to 0 (-20 K/hour to 0)

0

Heat rec ramp

(heating optimum start gradient)

0 to 36 DDF/hour (0 to 20 K/hour)

0