Switching levels, Zone options, Miscellaneous – Honeywell EXCEL 10 W7752D User Manual
Page 31

EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
EN2B-0285GE51
R0909
29
Switching Levels
See section "Configurations" on page 12 for more information about parameters.
Table 20. FCU Controller switching levels configuration options
function
configuration options
default
cooling stage 1 switching level
0 to 100%
5%
heating stage 1 switching level
0 to 100%
5%
cooling stage 2 switching level
0 to 100%
50%
heating stage 2 switching level
0 to 100%
50%
cooling stage 3 switching level
0 to 100%
75%
heating stage 3 switching level
0 to 100%
75%
cooling hysteresis
0 to 100%,
10%
heating hysteresis
0 to 100%
10%
Notes:
1. Stage switching levels and hysteresis are used for fan control as well as multi-stage heating/cooling outputs
control.
Zone Options
The Zone configuration options are listed in the following table. See section "Configurations" on page 12 for more information
about parameters.
Table 21. FCU Controller zone configuration options
function
configuration options
default
cooling occupied setpoint
50 to 95°F (10 to 35°C)
73.4°F (23°C)
heating occupied setpoint
50 to 95°F (10 to 35°C)
69.8°F (21°C)
cooling standby setpoint
50 to 95°F (10 to 35°C)
77°F (25°C)
heating standby setpoint
50 to 95°F (10 to 35°C)
66.2°F (19°C)
cooling unoccupied setpoint
50 to 95°F (10 to 35°C)
82.4°F (28°C)
heating unoccupied setpoint
50 to 95°F (10 to 35°C)
60.8°F (16°C)
Notes:
1. Ensure that unoccupied heating standby heating Miscellaneous The options available in the Miscellaneous tab are listed in the following table. See section "Configurations" on page 12 for more information about parameters. Table 22. FCU Controller miscellaneous configuration options function configuration options default Bypass time 0 to 1080 minutes 180 minutes Override priority last wins - the last command from either the wall module or from the network has priority. last wins Demand limit control bump 0 to 18 DDF (0 to 10 K) 3.6 DDF (2 K) Cool rec ramp (cooling optimum start gradient) -36 DDF/hour to 0 (-20 K/hour to 0) 0 Heat rec ramp (heating optimum start gradient) 0 to 36 DDF/hour (0 to 20 K/hour) 0
network wins - a network command always has priority until canceled.