Configure installer setup, Installer system tests, Caution – Honeywell COMMERCIALPRO TB7220U User Manual
Page 10

TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
62-0221—05
10
INSTALLER SETUP NUMBERS, SETTINGS, AND TESTS (TABLE 4)
Configure Installer Setup
1. Press and release the System key.
2. Press System and Done keys simultaneously.
3. Hold keys for approximately five seconds, until the
screen changes.
4. When the display changes, release the System and
Done keys.
NOTE: See Table 4 for installer setup (ISU) numbers
and settings.
Installer System Tests
Use the Installer System Test section to test the heating,
cooling and fan. Refer to the latter portion of Table 4.
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed
during Installer System Test
Avoid cycling compressor quickly.
IMPORTANT
Use Installer System Test to test heating, cooling
and fan. The setting chosen for System Type
(Installer Setup Number 0170) can prevent some
System Test Numbers from appearing.
Table 4. Installer Setup Menu.
Installer
Setup
Number
Installer Setup
Name
Default
Setting
All Settings
Notes
0120
Date (Year Upper)
20
20—20xx
21—21xx
Available year range: 2001 - 2178
0130
Date (Year Lower)
04
00-99
Available year range: 2001 - 2178
0140
Date (Month)
6
1-12
0150
Date (Day)
15
1-31 (Month Dependent)
0160
Schedule Options
4
0—Non-Programmable
4—Programmable
0170
System Selection
8
1—1H/1C Conv
2—1H/1C HP
3—1H w/o fan
4—1H with fan
6—1C
7—2H/1C HP (Aux. Heat)
8—2H/2C Conv
9—2H/1C Conv
10—1H/2C Conv
11—2H/2C HP
12—3H/2C HP (Aux.
Heat)
To use the Emergency Heat button, select setting
#7 or #12. See Fig. 16 or 17 for auxiliary heat
wiring.
0175
TOD/Economizer
output (terminal A)
0
0—Unused
1—TOD
2—Economizer
Economizer energizes A during a call for cool.
TOD energizes A during Occupied period, and de-
energizes A during Unoccupied.
0180
Heat Fan Operation 0
0—System controls fan
1—Thermostat controls
fan (ON during call for
heat)
Only shown for conventional system with heat
stages (ISU 0170) and fan capability selected.
If heat pump is selected, fan always operates with
Thermostat control.
The only thing that allows the fan to turn off during
occupied periods is a manual override of the fan
from On to Auto.
0185
Pre-occupancy
Purge Duration
0
0—no duration
1—one hour
2—two hours
3—three hours
Only shown if thermostat is programmable (ISU
0160).
Pre-occupancy purge enabled by nonzero duration
(and sends economizer to minimum position).
0190
Reversing Valve
O/B
0
0—O (O/B On Cool)
1—B (O/B On Heat)
Only shown with heat pump system selected.
0220
Cycles Per Hour
(CPH) for first stage
compressor
3
1-6
Only shown for system with cool stages (ISU
0170). Selection in this stage changes second
stage cool default CPH.
0230
CPH for second
stage compressor
3
1-6
Only shown for system with two stages of cool
(ISU 0170).